6. Safety instructions │ UK
17
6. Safety instructions
General
●
Assembly and electrical
connection may only be
undertaken by electricians in
accordance with chapter 2.
●
Read these operating
instructions carefully before
commissioning.
●
Only connect unit to perma-
nently wired electrical installa-
tions with NYM-O or NYM-J
(3 x 1.5 mm² or 5 x 1.5 mm²)
cables. Mains isolation device
required with contact
openings of at least 3 mm
at each pole.
●
The unit may only be
operated using the voltage
and frequency shown on the
rating plate.
●
Do not make any modifications
to the fan unit.
●
Never operate unit without
electronics cover [7] and
cover [4].
Safe and correct practices
during operation
Danger of injury caused
by objects in the impeller.
Do not insert any objects
in the unit.
Danger of injury from
rotating impeller. Do not
get too close to the fan
unit, to avoid hair,
clothing or jewellery being
drawn into the unit.
●
Risks for people (including
children) with reduced physical,
sensory or mental capabilities
or a lack of knowledge. Fan
may only be installed,
commissioned, cleaned and
maintained by people who can
safely recognise and avoid the
risks associated with this work.
Children must not play with the
unit.
Supply air intake within the
living area
●
The domestic air supply must
be set up so that virtually no
air from the kitchen, bathroom
and WC can flow into the
living areas in which the
AKE 150 is installed.
●
A room from which the air has
to be extracted must be fitted
with a non-closable, free
supply air cross section of at
least 150 cm², e.g. with Maico
door ventilation grille MLK.