4. Assembling the ventilation unit (Specialist installer)
4.7 Settings at the switchable power unit
DIP switches 3 +4 for fan level 2 (normal ventilation/daytime operation)
Volumetric flow
Switch 3
Switch 4
1= ON
135 m³/h
1
1
0 = OFF
120 m³/h
1
0
100 m³/h (factory
0
1
setting)
85 m³/h
0
0
DIP switches 5 +6 for fan level 1 (basic ventilation/nighttime operation)
Volumetric flow
Switch 5
Switch 6
1= ON
105 m³/h
1
1
0 = OFF
95 m³/h
1
0
85 m³/h
0
1
70 m³/h (factory
0
0
setting)
Anti-frost protection:
The ventilation unit is fitted with a frost protection, as any condensation
in the heat exchanger could freeze in the case of low, outside
temperatures.
The outside air flow is reduced so that there is no further risk of freezing.
The frost protection is fixed at the factory setting.
Adjusting the volumetric flow on the exhaust air side
There is a potentiometer (P2) on the ventilation unit's switchable power unit for
adjusting the exhaust air volumetric flow to the supply air volume flow. This
setting may only be made by MAICO Customer service.
■
Anticlockwise = Reducing the exhaust air volumetric flow
■
Clockwise = Increasing the exhaust air volumetric flow
17
i
Summary of Contents for Aeronom WS 150
Page 6: ...2 Das Lüftungssystem 4 ...
Page 10: ...2 Das Lüftungssystem 2 8 Lüftungsgerät Übersicht 8 ...
Page 23: ......
Page 30: ...2 The ventilation system 4 ...
Page 34: ...2 The ventilation system 2 8 Ventilation unit Overview 8 ...
Page 54: ...2 Le système de ventilation 4 ...
Page 58: ...2 Le système de ventilation 2 8 Appareil de ventilation Vue d ensemble 8 ...
Page 71: ......