Using an AGS Module: Operation/Monitoring
7.2.6
AGS Remote Status Messages
A status message may be an operational or fault message. Access the AGS status menu (
METER:
04A AGS Status
menu) to view the AGS’s current operating status. This menu is important when
determining if the AGS is working correctly, or for troubleshooting an AGS installation.
7.2.6.1 AGS Remote Operational Statuses
Table 7-3 below has a brief description of possible AGS operational statuses.
Status
Description
AC In
The inverter/charger is connected to another source such as a grid or an
alternate generator, and is not controlled by the AGS. When
AC In
displays,
the AGS is prevented or locked out from all autostarting conditions, except
for when the generator needs to exercise—if enabled.
Gen Cooldown
The autostop setting has been met in one of the generator autostart/au-
tostop menus and the generator has been disconnected from the inverter/
charger. However, the generator still runs until the cooldown time is met
(as per the
SETUP: 04J Gen Cooldown Time
setting).
Gen Warmup
The AGS is attempting to start the generator and a time period has been
set from the
SETUP: 04I Gen Warm-up Time
menu. Once the AGS status
indicates “
Warm-up
”, the inverter/charger’s AC input ignores any incoming
AC power. This prevents the inverter/charger from loading the generator
during warm-up. Once the AGS has determined that the generator is run-
ning, the warm-up time setting must be met before the generator can con-
nect to the inverter/charger.
Manual Run
Generator started manually from a start/stop switch directly connected to
the generator, or from the
CTRL: 03 Gen Control
menu.
Note:
The AGS determines that the generator has been manually turned on by sensing a gen
run sense voltage to Terminal #2 on the AGS’s 8-port terminal block. However, if the Gen Type
DIP switch is set to “
2-Wire Standby
” (which doesn’t require a gen run sense voltage), manually
turning the generator on displays a status of “
AC In
” rather than “
Manual Run
”.
No Comm
The AGS is not communicating with the inverter/remote.
AGS not present
If an AGS is installed, then refer to Section 7.3.2 “Resolving AGS Opera-
tional Statuses” for assistance.
Off
The
CTRL: 03 Gen Control
menu is set to
OFF
. This setting will not allow the
AGS to autostart the generator.
Quiet Time
The AGS has entered Quiet Time per the
SETUP: 04G Quiet Time
setting.
Note:
The generator will not autostart during Quiet Time.
Ready
The
CTRL: 03 Gen Control
menu is set to
AUTO
, and the AGS is ready to
autostart the generator based on the active autostart settings under the
SETUP: 04 AGS Setup
menus.
Table 7-3, AGS Remote Operational Statuses