Using an AGS Module: Operation/Monitoring
Figure 7-3, AGS SETUP Menu Map (Section 2)
Note:
MS-PAE, MS-PE & MSH Series models only
Default: OFF
04B Gen Run Time
OFF
Set Stop Gen
AM-PM =
00:00
A
Set Stop Gen
Minute =
00:
00
P
Set Gen Run Time
OFF
Set Start Gen
AM-PM =
00:00
A
Set Stop Gen
Hour = 1
:00P
Set Start Gen
Hour = 1
:00A
Set Start Gen
Minute =
00:
00
A
Set Gen Run Time
ON
Set Start Gen
Hour = 12
:00A
...
Set Start Gen
Minute =
00:
45
A
...
Set Start Gen
AM-PM =
00:00
P
Set Stop Gen
Hour = 12
:00P
Set Stop Gen
Minute =
00:
45
P
Set Stop Gen
AM-PM =
00:00
P
...
...
Default:
OFF
P
R
R
R
R
P
P
P
P
P
P
SETUP
Set Stop Gen
Volts = 9.1
04A Gen Run VDC
11.5 to 14.4
Set Start Gen
Volts = OFF
Set Start Volts
Delay = 0 Sec
Set Stop Volts
Delay = 0 Sec
Set Start Gen
Volts = 11.5
Set Start Gen
Volts = 15.9
...
Set Start Volts
Delay = 120 Sec
Set Start Volts
Delay = 127 Min
...
Set Stop Volts
Delay = 120 Sec
Set Stop Volts
Delay = 127 Min
...
SETUP Menu continues on next page
...
...
...
...
...
Start Volts Ranges:
12v = 9.0-15.9 VDC;
24v = 18.0-31.8 VDC; 48v = 36.0-63.6 VDC
Stop Volts Ranges:
12v = 9.1-16.0 VDC;
24v = 18.2-32.0 VDC; 48v = 36.4-64.0 VDC
Set Stop Gen
Volts = 14.4
Set Stop Gen
Volts = Float
P
P
P
P
P
R
[Status/Fault]
04 AGS Setup
Set Stop Gen AC
Amps = 4A
Set Stop Amps
Delay = 0 Sec
04C Gen Run Amps
OFF
Set Start Gen AC
Amps = OFF
Set Start Amps
Delay =
0 Sec
Set Start Gen AC
Amps = 5A
Set Start Gen AC
Amps = 60A
...
Set Start Amps
Delay = 120 Sec
Set Start Amps
Delay = 127 Min
...
Set Stop Amps
Delay = 120 Sec
Set Stop Amps
Delay = 127 Min
...
...
...
Set Stop Gen AC
Amps = 20A
Set Stop Gen AC
Amps = 59A
...
...
P
R
R
P
P
P
P