57-642 ECLIPSE Model 705 Guided Wave Radar Transmitter for Hygienic Industries
Reference Conditions
Reflection from water at +70° F (+20° C) with 72" (183 cm) coaxial probe
(CFD threshold)
Linearity
<0.3% of probe length or 0.3 inch (. mm) (whichever is greater)
Measured Error
±0.5% probe length or ±0.5 inch (13 mm) (whichever is greater)
Resolution
±0.1 inch (3 mm)
Repeatability
<0.1 inch (3 mm)
Hysteresis
<0.1 inch (3 mm)
Response Time
<1 second
Warm-up Time
<5 seconds
Operating Temp. Range
-40 to +175 °F (-40 to +80 °C)
LCD Temp. Range
-5 to +160 °F (-20 to +70 °C)
Ambient Temp. Effect
Approxi0.02% of probe length/ °C
Process Dielectric Effect
<0.3 inch (8 mm) within selected range
Humidity
0-99%, non-condensing
7.2 Performance - Model 705
Environment
Operating Temperature
-40 to +175 °F
(-40 to +80 °C)
Display Function Operating Temperature
-5 to +160 °F
(-20 to +70 °C)
Storage Temperature
-50 to +175 °F
(-46 to +80 °C)
Humidity
0-99%, non-condensing
Electromagnetic Compatibility
Meets CE Requirements: EN 61326
Note: Single Rod probes must be used in metallic vessel or stillwell to
maintain CE requirement.
Mounting Affects: Single Rod
Nozzles do not restrict performance by ensuring the following:
No nozzle is <2" (50 mm) diameter
Ratio of Diameter: Length is 1:1 or greater;
any ratio <1:1 (e.g., a 2"
×
6" nozzle = 1:3) may require a Blocking
Distance and/or DIELECTRIC adjustment (see Section 2.6.5)
No pipe reducers are used
Obstructions: may require configuration changes
Keep conductive objects away from probe to ensure proper performance
Shock Class
ANSI/ISA-S71.03 Class SA1
Vibration Class
ANSI/ISA-S71.03 Class VC2
SIL 3 Capable
Safe Failure Fraction (SFF) 91%