17
57-642 ECLIPSE Model 705 Guided Wave Radar Transmitter for Hygienic Industries
2.6.5.1
Measurement Type: Level Only (Loop Control = Level)
Display
Action
Comment
12
Senstvty
xxx
Enter
value upward or
downward to sense liquid
surface
Allows fine gain adjustment for single rod probes (this parameter
is password protected for coaxial and twin rod probes).
13
LoopCtrl
(select)
Select
variable to control
loop current
Select Level
14
Set 4mA
xxx.x 1u
Enter
the PV value for the
4 mA point
A small transition zone (0–6" [0–15cm] ) may exist at the top/bot-
tom of the probe. See
Functional Specifications Probe, Section
3.6.1
15
Set 20mA
xxx.x lu
Enter
the PV value for the
20 mA point
A small transition zone (0–6" [0–15cm] ) may exist at the top/bot-
tom of the probe. See
Functional Specifications Probe, Section
3.6.1
16
Damping
xx s
Enter
time constant of
desired damping
A Damping factor (0–10 seconds) may be added to smooth the
output due to turbulence
17
Fault
(select)
Select
the loop current value
in presence of a fault
Select from
3.6 mA, 22 mA
or
HOLD
18
BlockDis
xx.x lu
Enter distance below refer-
ence point where level is not
sensed
Allows user to ignore level measurements near the top of the
probe
19
SZ Fault
(select)
Select
loop current behavior
when level is sensed in safety
zone
Safety Zone
is a user-defined area just below the
Blocking
Distance
. Enable Fault if necessary to ensure safe, reliable high-
level readings in critical applications. Choices are
None, 3.6 mA
,
22 mA
,
Latch 3.6
or
Latch 22
. If
Latch 3.6
or
Latch 22
is
selected, the loop current will remain in alarm until it is manually
cleared with the SZ Alarm Reset below (#21)
20
SZ Height
(xx.x lu)
Enter
distance below
BlockDis where SZ Fault will
be asserted
Enter a distance value that develops a safety zone just below the
Blocking Distance
. Here the unit will report a
Safety Zone Fault
(#19) if the level rises into this area.
21
SZ Alarm Reset
Press Enter
to clear a
latched Safety Zone alarm
Clear a latched
Safety Zone
alarm
22
Threshld
(select)
Select
the type of threshold
Unit default
CFD
. Only select
Fixed
in application with low
dielectric material over higher dielectric material and unit is read-
ing incorrect level. Example: Oil over water. (Adjustment of
Trim
Level
may be necessary when threshold is changed)
23
Poll Adr
xx
Enter
HART polling address
number (0-63)
Select a HART poll address (0–63). Enter 0 for a single
transmitter installation. Poll address does not affect loop current.
24
Loop Mode
Enable/Disable
Determines whether the loop is fixed at 4.0 mA or controlled by
the PV.
25
Trim Lvl
xx.x lu
Enter
value to adjust Level
reading
-10.0 inches
≤
Lvl Trim
≤
+10.0 inches
(Requires superuser password)
26
Trim 4
xxxx
Fine tune the 4 mA point
Adjust setting to output exactly 4.0 mA on current meter
27
Trim 20
xxxx
Fine tune the 20 mA point
Adjust setting to output exactly 20.0 mA on current meter
28
Loop Tst
xx.x mA
Enter
a mA Output value
Set mA output to any given value to perform loop test
29
LvlTicks
Xxxxx
Diagnostic Display
Time of flight from fiducial to level signal
30
New Pass
xxx
Enter
new password (0-255)
Displays encrypted value of present password
31
Language
(select)
Select
from English, Spanish,
French, German
Language choice for LCD display
32
Mdl705HT
Ver3.0a0
Transmitter display
Product identification Firmware version