45
57-600 Eclipse
®
Guided Wave Radar Transmitter
3.3.2 Status Messages
Display Message
Action
Comment
Lo Temp
Present temperature in
electronics compartment is
below -40 °C
1) Transmitter may need to be moved to ensure ambient temperature
is within specification
2) Change to remote mount transmitter
HiVolAlm
Level more than 5% above
highest point in strapping table
Verify strapping table is entered correctly. None. Signal amplitude is
lower than desired.
Sys Warn
Unexpected but non-fatal
software event
Consult factory
TrimReqd
Factory set Loop values are
defaults, loop output may be
inaccurate
Consult factory
Cal Reqd
Factory set default calibration
parameters are in use, level
reading may be inaccurate
Consult factory
SlopeErr
Ramp circuit generating
improper voltage
Consult factory
LoopFail
Loop current differs from
expected value
Consult factory
No Ramp
No End-of-Ramp signal detected Consult factory
DfltParm
Internal non-volatile parameters
have been defaulted
Consult factory
LVL < Probe
Length
Apparent position of the upper
level pulse is beyond the end of
probe.
1) Check entered probe length
2) Change threshold to fixed
EE Fail
EEPROM error allowing watch-
dog timer to expire
Consult factory
CPU Fail
A-D converter time out allowing
watchdog timer to expire
Consult factory
SfwrFail
A fatal software error allowing
watchdog timer to expire
Consult factory
PACT
ware
™
PC Program
The ECLIPSE Model 705 offers the ability to do Trending and Echo Curve analysis using a PACT
ware
DTM.
This is a powerful troubleshooting tool that can aid in the resolution of some of the Error Messages shown above.
Refer to Bulletins 59-101 and 59-601 for more information.