25
57-600 Eclipse
®
Guided Wave Radar Transmitter
2.6.5.2
Measurement Type: Level and Volume (Loop Control = Volume)
Display
Action
Comment
22
SZ Fault
(select)
Select
loop current behavior
when level is sensed in safety
zone
Safety Zone
is a user-defined area just below the
Blocking
Distance
. Enable Fault if necessary to ensure safe, reliable high-
level readings in critical applications. Choices are
None, 3.6 mA
,
22 mA
,
Latch 3.6
or
Latch 22
. If
Latch 3.6
or
Latch 22
is
selected, the loop current will remain in alarm until it is manually
cleared with the SZ Alarm Reset below (#23)
23
SZHeight
xx.x lu
Enter
distance below
BlockDis where SZ Fault will
be asserted
Enter a distance value that develops a safety zone just below the
Blocking Distance
. Here the unit will report a
Safety Zone Fault
(#21) if the level rises into this area.
24
SZ Alarm Reset
Press Enter
to clear a
latched Safety Zone alarm
Clear a latched
Safety Zone
alarm
25
Threshld
(select)
Select
the type of threshold
Unit default
CFD
. Only select
Fixed
in application with low
dielectric material over higher dielectric material and unit is read-
ing incorrect level. Example: Oil over water. (Adjustment of
Trim
Level
may be necessary when threshold is changed)
26
Poll Adr
xx
Enter
HART polling address
number (0-63)
Select a HART poll address (0–63). Enter 0 for a single
transmitter installation. Poll address does not affect loop current.
27
Loop Mode
Enable/Disable
Determines whether the loop is fixed at 4.0 mA or controlled by
the PV.
28
Trim Lvl
xx.x lu
Enter
value to adjust Level
reading
-10.0 inches <= Lvl Trim <= +10.0 inches
(Requires superuser password)
29
Trim 4
xxxx
Fine tune the 4 mA point
Adjust setting to output exactly 4.0 mA on current meter
30
Trim 20
xxxx
Fine tune the 20 mA point
Adjust setting to output exactly 20.0 mA on current meter
31
Loop Tst
xx.x mA
Enter
a mA Output value
Set mA output to any given value to perform loop test
32
LvlTicks
xxxx
Diagnostic Display
Time of flight from fiducial to level signal
33
New Pass
xxx
Enter
new password (0-255)
Displays encrypted value of present password
34
Language
(select)
Select
from English, Spanish,
French, German
Language choice for LCD display
35
Mdl705HT
Ver3.0a0
Transmitter display
Product identification Firmware version
36
DispFact
(select)
Select
Yes to display factory
parameter menus
Allows for viewing the factory parameters
37
History
(current status)
Press Enter
to view history
of recent exceptions
Diagnostic Display
38
HF cable
(select)
Superuser Parameter
Select from 3-foot or 12-foot remote
39
Run Time
40
History Reset
Press Enter
and select yes
to clear history
Similar to SZ Alarm Reset
41
FidTicks
xxxx
Diagnostic Display
Time of flight from start of ramp to fiducial
42
Fid Type
(select)
Superuser Password
Select from positive or negative
(Selection only allowed for some probes)
43
Fid Spread