background image

28

57-600 Eclipse

®

Guided Wave Radar Transmitter

2.6.5.3

Measurement Type: Interface Level (Loop Control = Interface Level)

Display

Action

Comment

21

SZ Fault

(select)

Select

loop current behavior

when level is sensed in safety
zone

Safety Zone 

is a user-defined area just below the 

Blocking

Distance

. Enable Fault if necessary to ensure safe, reliable high-

level readings in critical applications. Choices are 

None, 3.6 mA

,

22 mA

Latch 3.6

or 

Latch 22

. If 

Latch 3.6

or 

Latch 22

is 

selected, the loop current will remain in alarm until it is manually
cleared with the SZ Alarm Reset below (#23)

22

SZ Height

xx.x lu

Enter 

distance below

BlockDis where SZ Fault will
be asserted

Enter a distance value that develops a safety zone just below the

Blocking Distance

. Here the unit will report a 

Safety Zone Fault

(#21) if the level rises into this area.

23

SZ Alarm Reset

Press Enter

to clear a

latched Safety Zone alarm

Clear a latched 

Safety Zone

alarm

24

Threshld

(select)

Select

from CFD, Fixed

For interface, refers to threshold for upper level pulse. (Set to
Fixed for most common applications.)

25

IfcThrsh

(select)

Select

from CFD, Fixed

Interface mode only. Threshold for interface level pulse. (Set to
CFD for most common applications.)

26

Poll Adr

xx

Enter 

HART polling address

number (0-63)

Select a HART poll address (0–63). Enter 0 for a single
transmitter installation. Poll address does not affect loop current.

27

Loop Mode

Enable/Disable

Determines whether the loop is fixed at 4.0 mA or controlled by
the PV.

28

Trim Lvl

xx.x lu

Enter 

value to adjust Level

reading

-10.0 inches <= Lvl Trim <= +10.0 inches

(Requires superuser password)

29

Trim 4

xxxx

Fine tune the 4 mA point

Adjust setting to output exactly 4.0 mA on current meter

30

Trim 20

xxxx

Fine tune the 20 mA point

Adjust setting to output exactly 20.0 mA on current meter

31

Loop Tst

xx.x mA

Enter 

a mA Output value

Set mA output to any given value to perform loop test

32

LvlTicks

xxxx

Diagnostic Display

Time of flight from fiducial to interface signal

33

IfcTicks

xxxx

Diagnostic Display

Interface mode only. Time of flight through upper liquid

34

Medium

Diagnostic Display

Interface mode only. Displayed messages are: Unknown,
Oil Only, Thin Oil, Thick Oil, Dry Probe

35

New Pass

xxx

Enter

new password (0-255)

Displays encrypted value of present password

36

Language

(select)

Select

from English, Spanish,

French, German

Language choice for LCD display. (no HART counterpart)

37

Mdl705HT

Ver3.0a0

Transmitter display

Product identification. Firmware version

38

DispFact

(select)

Select

Yes to display factory

parameter menus

Access for viewing the factory parameter

39

History

(current status)

Press Enter

to view history

of recent exceptions

Diagnostic Display

40

Run Time

41

History Reset

Press Enter

and select yes

to clear history

Similar to SZ Alarm Reset

42

HF cable

(select)

Superuser Parameter

Select from 3-foot or 12-foot remote

Summary of Contents for eclipse 705

Page 1: ...Guided Wave Radar Level Transmitter Enhanced Model 705 Software v3 x Installation and Operating Manual 2014 68 EU...

Page 2: ...ctrostatic sensitive components This device complies with Part 15 of the FCC rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This devi...

Page 3: ...rocedure 21 2 6 5 1 Measurement Type Level Only 21 2 6 5 2 Measurement Type Level and Volume 24 2 6 5 3 Measurement Type Interface Level 27 2 6 5 4 Measurement Type Interface and Volume 30 2 6 6 Offse...

Page 4: ...s a minimum of 6 150 mm below the process connection This may include utilizing a nozzle or spool piece to raise the probe Consult fac tory to ensure proper installation 1 1 Getting Started Before beg...

Page 5: ...range of the process medium Upper layer dielectric for interface applications _____________ Loop Control Is the output current to be controlled by level or volume _____________ Set 4 0 mA What is the...

Page 6: ...ly recommended to obtain 45 ft lbs This is a critical connection DO NOT LEAVE HAND TIGHT NOTE Universal connector can be supplied with lock screws for applications with significant vibration Contact f...

Page 7: ...ired for configuration the default password is 0 from the LCD keypad 7 Lvl Units xxx LvlUnits xxx PrbModel select Probe Ln xxx x LvlOfst xxx x Dielctrc select Set 4mA xxx x Set 20mA xxx x Select the P...

Page 8: ...erence when ordering parts Model Number Serial Number 2 2 Electrostatic Discharge ESD Handling Procedure Magnetrol electronic instruments are manufactured to the highest quality standards These instru...

Page 9: ...the process connection size and type Coaxial probe 11 2 38 mm twin rod probe 17 8 47 mm transmitter 11 2 38 mm A torque wrench is highly desirable Flat blade screwdriver Digital multimeter or digital...

Page 10: ...ure pressure dielectric and viscosity are within the probe specifications for the installation See Specifications Section 3 6 Model 7xD High Temp High Pressure probes should be handled with extra care...

Page 11: ...be is acceptable 2 4 2 1 To install a rigid twin rod probe Make sure the process connection is at least 2 NPT or a flanged mounting Make sure that there is at least 1 25 mm spacing between the active...

Page 12: ...0 32 set screws 3 on both securing devices using a 3 32 2 5 mm hex wrench and slide the securing devices off of the probe c Slide the TFE weight off of the probe d Cut and remove the required cable 4...

Page 13: ...d connections tighten the hex nut of the probe process connection For flanged connections tighten flange bolts Probe can be stabilized by placing into a non metallic cup or bracket at the bottom of th...

Page 14: ...designed for a 3000 lb 1360 kg pull down force for use in applications such as sand plastic pellets and grains It is offered with a maximum 75 foot 22 meter probe length Model 7x2 Single Rod dielectri...

Page 15: ...s f Slide the weight back on to the probe g Reinstall the two cable clamps and tighten h Enter the new probe length inches or cm in software 2 4 4 4 To install a Model 7x2 bulk solids flexible single...

Page 16: ...tter is facing the desired direction use a 11 2 38 mm wrench to tighten the universal connection on the transmitter to 45 ft lbs A torque wrench is highly rec ommended This is a critical connection DO...

Page 17: ...dive Cl I Div 2 A general purpose installation does not have flammable media present Areas rated non incendive Cl I Div 2 have flammable media present only under abnormal conditions No special electri...

Page 18: ...uipment for installation in hazardous areas A hazardous location is an area in which flammable gases or vapors are or may be present in the air in quantities sufficient to produce explo sive or ignita...

Page 19: ...ION fieldbus information 2 6 1 Operating Parameters Some key information is needed to calibrate the ECLIPSE transmitter Complete the configuration information table in Section 1 1 2 2 6 2 Setting Up f...

Page 20: ...r Enters the configuration mode Accepts a value and moves noted by an exclamation point to the next step of the as the last character in the top configuration program display line 2 6 4 Password Prote...

Page 21: ...Transmitter Display LoopCtrl Level Transmitter default display showing Status Level Output and Loop values cycles every 5 seconds 2 Level xxx x Transmitter Display Transmitter displays Level Value in...

Page 22: ...main in alarm until it is manually cleared with the SZ Alarm Reset below 21 20 SZ Height xx x lu Enter distance below BlockDis where SZ Fault will be asserted Enter a distance value that develops a sa...

Page 23: ...tic parameter 46 Pos Ampl xxx Superuser Password Diagnostic parameter 47 Signal xxx Diagnostic Display Indication of level signal amplitude 48 Compsate select Superuser Password Select from None Manua...

Page 24: ...x lu Enter desired Level reading when probe is dry Level Offset is the distance from the probe tip to the desired 0 level point 90 to 300 Refer to Section 2 6 6 12 VolUnits select Select the volume un...

Page 25: ...ingle transmitter installation Poll address does not affect loop current 27 Loop Mode Enable Disable Determines whether the loop is fixed at 4 0 mA or controlled by the PV 28 Trim Lvl xx x lu Enter va...

Page 26: ...sword Diagnostic factory setting 50 Signal xxx Diagnostic Display Indication of level signal amplitude 51 Compsate select Superuser Parameter Select from None Manual Auto 52 7xKCorr xxx Superuser Para...

Page 27: ...nter the desired reading when probe is dry Level Offset is the distance from the probe tip to the desired 0 level point 90 to 300 Refer to Section 2 6 6 12 Upr Diel select Enter the dielectric constan...

Page 28: ...ter installation Poll address does not affect loop current 27 Loop Mode Enable Disable Determines whether the loop is fixed at 4 0 mA or controlled by the PV 28 Trim Lvl xx x lu Enter value to adjust...

Page 29: ...Calibration parameter 49 Scl Ofst xxx Factory Parameter Calibration parameter 50 Neg Ampl xxx Superuser Password 51 Ifc Ampl Superuser Password 52 Pos Ampl xxx Superuser Password 53 Signal xxx Diagnos...

Page 30: ...x x lu Enter the desired reading when probe is dry Offset is the distance from the probe tip to the desired 0 level point 90 to 300 Refer to Section 2 6 6 14 VolUnits select Select the volume units Se...

Page 31: ...l Adr xx Enter HART polling address number 0 63 Select a HART poll address 0 63 Enter 0 for a single transmitter installation Poll address does not affect loop current 31 Loop Mode Enable Disable Dete...

Page 32: ...ameter 53 Scl Ofst xxx Factory Parameter Calibration parameter 54 Neg Ampl xxx Superuser Parameter 55 Ifc Ampl Superuser Parameter 56 Pos Ampl xxx Superuser Parameter 57 Signal xxx Diagnostic Display...

Page 33: ...e 4 mA point at 24 inches and the 20 mA point at 60 inches as referenced from the bottom of the tank When the ECLIPSE transmitter is mounted in a chamber bridle it is usually desirable to configure th...

Page 34: ...ts do not have to be used unused points should be left at 0 2 Strapping table point values can be entered or changed in any order 3 All strapping table points must be monotonic and sequential In other...

Page 35: ...e terminal block in the electronics housing of the ECLIPSE transmitter HART uses the Bell 202 frequency shift keying technique of high frequency digital signals It operates on the 4 20 mA loop and req...

Page 36: ...2 Trim Level 23 Date Time Initials 5 Probe Length 1 Probe Model 2 Probe Mount 1 Faults 2 Warnings 1 Loop Test 2 Present Status 3 Status History 4 Level Ticks 5 Fiducial Ticks 6 Fiducial Spread 7 Signa...

Page 37: ...ith the H1 Foundation Fieldbus protocol operating at 31 25 kbits sec The H1 physical layer is an approved IEC 61158 standard The figure on page 38 shows a typical Fieldbus installation An IEC61158 shi...

Page 38: ...regardless of manufacturer without a loss of functionality All FOUNDATION fieldbus devices must be tested for interoperability by the Fieldbus Foundation MAGNETROL Model 705FF device registration info...

Page 39: ...ability The DD provides extended descriptions for each object and provides pertinent information needed by the host system DDs are similar to the drivers that your personal computer PC uses to operate...

Page 40: ...is a revolutionary new level measurement technology The ECLIPSE electronics are housed in an ergonomic hous ing comprised of two tandem compartments angled at a 45 degree angle for ease of wiring and...

Page 41: ...rface some of the energy continues down the length of the probe through the upper liquid The pulse is again reflected when it reaches the higher dielectric lower liquid refer to figure at left Since t...

Page 42: ...ECLIPSE transmitter a waveguide with a characteristic impedance in air is used as a probe When part of the probe is immersed in a material other than air there is lower impedance due to the increase i...

Page 43: ...enter for the read Universal Commands DDs are not installed in handheld latest DDs Level Reading on Display is stuck at Software believes probe is flooded Check actual level If probe is not flooded fu...

Page 44: ...electric range 3 Replace with Model 7xR Overfill probe NoSignal No level signal being detected 1 Ensure dielectric setting is correct for measured medium 2 Increase sensitivity 3 Confirm that the prob...

Page 45: ...Ramp circuit generating improper voltage Consult factory LoopFail Loop current differs from expected value Consult factory No Ramp No End of Ramp signal detected Consult factory DfltParm Internal non...

Page 46: ...to form a clog or bridge between the elements causes the greatest degrada tion in performance High dielectric media e g water based will show as level at the location of the bridging Stratification I...

Page 47: ...ELECTRIC RANGE a small amount to aid in reducing echoes in nozzle Increasing the DIELECTRIC setting reduces the gain which may cause instrument to lose level of lower dielectric media consult factory...

Page 48: ...TANT Measured media inside vessel must be non flammable only If media inside vessel is flammable then the explosion proof version which contains an internal barrier making the probe Intrinsically Safe...

Page 49: ...49 57 600 Eclipse Guided Wave Radar Transmitter 3 4 2 Agency Specifications Intrinsically Safe Installation...

Page 50: ...50 57 600 Eclipse Guided Wave Radar Transmitter 3 4 3 Agency Specifications FoundAtIon fieldbus System...

Page 51: ...Viton Z12 2201 237 Consult Factory for alternative O ring materials Housing cover without glass 004 9225 002 Housing cover with glass GP IS 036 4410 001 XP 036 4410 003 7xB Twin Rod Probe Shortening...

Page 52: ...0 20 30 40 VDC GENERAL PURPOSE GP INTRINSICALLY SAFE IS EXPLOSION PROOF XP 20 5 mA 24 VDC 630 11 Maximum temperature of O ring not necessarily maximum process temperature Material Code Maximum Tempera...

Page 53: ...l 7xB probe 1 2 inches 30 mm Specification for top 48 inches of single rod will be application dependent Accuracy may degrade when using manual or automatic compensation 57 600 Eclipse Guided Wave Rad...

Page 54: ...r 800 F 1500 psig 427 C 103 bar 400 F 5500 psig 200 C 380 bar 7xQ 650 F 2400 psig 340 C 165 bar 7xS 575 F 1275 psig 300 C 88 bar Maximum Process Pressure 1000 psig 70 F 70 bar 20 C 1000 psig 70 F 70 b...

Page 55: ...375 clearance between rods Two 25 6 mm dia cables 875 22 mm CL to CL 3125 8 mm diameter rod 875 10 mm diameter tube 6 15mm dia rod 1 75 44mm dia tube 6 15 mm diameter rod 1 75 44 mm diameter tube Pro...

Page 56: ...0 40 60 80 100 120 140 160 100 150 200 250 Ambient Temperature F 300 Process Temperature F Ambient Temperature vs Process Temperature 350 400 180 200 0 100 200 300 400 500 600 700 800 900 1000 1100 12...

Page 57: ...cess Conn 45 H 10 08 256 4 00 102 D Eclipse with 7xD Probe Threaded Connection Eclipse with 7xD Probe Flanged Connection Eclipse with 7xG Probe max 240 6 1 m 4 12 105 3 28 83 4 00 102 Elect Conn Qty 2...

Page 58: ...t 10 oz 284 grams 3 00 76 3 00 76 Eclipse with 7x5 Twin Rod Bulk Solids Flexible Probe Flanged or NPT Connection 3 25 83 Probe Insertion Length 0 1875 Cable 316SS Weight 2 0 50 Probe Insertion Length...

Page 59: ...57 1 25 3 88 99 TFE Weight 1 lb 454 grams 2 0 50 2 24 57 NPT Process Connection 7X1 12 00 305 7X2 3 00 76 0 1875 5 Cable Eclipse with 7x2 Bulk Solids Flexible Probe Flanged or NPT Connection 3 25 83 P...

Page 60: ...osion Proof FM CSA Non incendive A Integral General Purpose Intrinsically Safe ATEX JIS EEx ia IIC T4 B Remote General Purpose Intrinsically Safe ATEX JIS EEx ia IIC T4 C Integral Explosion Proof ATEX...

Page 61: ...P 5P 6P and 9P only J 316 316L SST NACE Construction K 316 316L stainless steel probe and process connection ASME B31 1 specifications model 7xS only N Enlarged coaxial probe 316 316L stainless steel...

Page 62: ...37 11 2 900 1500 ANSI Raised Face Flange 38 11 2 2500 ANSI Raised Face Flange 43 2 150 ANSI Raised Face Flange 44 2 300 ANSI Raised Face Flange 45 2 600 ANSI Raised Face Flange 47 2 900 1500 ANSI Rai...

Page 63: ...0 DIN 2527 Form E Flange EH DN 80 PN 320 DIN 2527 Form E Flange EJ DN 80 PN 400 DIN 2527 Form E Flange FA DN 100 PN 16 DIN 2527 Form B Flange FB DN 100 PN 25 40 DIN 2527 Form B Flange FD DN 100 PN 64...

Page 64: ...user from installing an external XP seal adjacent within 18 to the device Fault A defect or failure in a circuit The current mA value unit defaults to 3 6 22 or Hold when a diagnostic condition occurs...

Page 65: ...he choices are in inches and cm centimeters Waveguide See Probe Window A time slice variable that enhances system resolution Factory setting Intrinsic Safety A design or installation approach that lim...

Page 66: ...be Mount Measurement Type Level Units Probe Length Level Offset Volume Units opt Strapping Table opt Dielectric Sensitivity Loop Control 4mA point 20mA point Damping Blocking Distance Safety Zone Faul...

Page 67: ...em Value Value Value TROUBLESHOOTING Working Value Non Working Value FidTicks FidSprd Fid Type Fid Gain Window Conv Fct Scl Ofst Neg Ampl Pos Ampl Signal Compsate DrateFct Targ Ampl Targ Tks Targ Cal...

Page 68: ...applicability of our warranty No claims for misapplication labor direct or consequen tial damage will be allowed Return Material Procedure So that we may efficiently process any materials that are ret...

Reviews: