31
57-600 Eclipse
®
Guided Wave Radar Transmitter
2.6.5.4
Measurement Type: Interface and Volume
Display
Action
Comment
24
BlockDis
xx.x lu
Enter
distance below
reference point where level is
not sensed
Allows user to ignore level measurements near the top of the
probe
25
SZ Fault
(select)
Select
lop current behavior
when level is sensed in safety
zone
Safety Zone
is a user-defined area just below the
Blocking
Distance
. Enable Fault if necessary to ensure safe, reliable high-
level readings in critical applications. Choices are
None, 3.6 mA
,
22 mA
,
Latch 3.6
or
Latch 22
. If
Latch 3.6
or
Latch 22
is
selected, the loop current will remain in alarm until it is manually
cleared with the SZ Alarm Reset below (#27)
26
SZ Height
xx.x lu
Enter
distance below
BlockDis where SZ Fault will
be asserted
Enter a distance value that develops a safety zone just below the
Blocking Distance
. Here the unit will report a
Safety Zone Fault
(#25) if the level rises into this area.
27
SZ Alarm Reset
Press Enter
to clear a
latched Safety Zone alarm
Clear a latched
Safety Zone
alarm
28
Threshld
(select)
Select
from CFD, Fixed
For interface, refers to threshold for upper level pulse. (Set to
Fixed for most common applications.)
29
IfcThrsh
(select)
Select
from CFD, Fixed
Interface mode only. Threshold for interface level pulse. (Set to
CFD for most common applications.)
30
Poll Adr
xx
Enter
HART polling address
number (0-63)
Select a HART poll address (0–63). Enter 0 for a single
transmitter installation. Poll address does not affect loop current.
31
Loop Mode
Enable/Disable
Determines whether the loop is fixed at 4.0 mA or controlled by
the PV.
32
Trim Lvl
xx.x lu
Enter
value to adjust Level
reading
-10.0 inches <= Lvl Trim <= +10.0 inches
(Requires superuser password)
33
Trim 4
xxxx
Fine tune the 4 mA point
Adjust setting to output exactly 4.0 mA on current meter
34
Trim 20
xxxx
Fine tune the 20 mA point
Adjust setting to output exactly 20.0 mA on current meter
35
Loop Tst
xx.x mA
Enter
a mA Output value
Set mA output to any given value to perform loop test
36
LvlTicks
Xxxxx
Diagnostic Display
Time of flight from fiducial to interface signal
37
IfcTicks
Xxxxx
Diagnostic Display
Interface mode only
Time of flight through upper liquid
38
Medium
Diagnostic Display
Interface mode only
Displayed messages are: Unknown, Oil Only, Thin Oil, Thick Oil
39
New Pass
Xxx
Enter
new password (0-255)
Displays encrypted value of present password
40
Language
(select)
Select
from English, Spanish,
French, German
Language choice for LCD display. (no HART counterpart)
41
Mdl705HT
Ver3.0a0
Transmitter display
Product identification. Firmware version
42
DispFact
(select)
Select
Yes to display factory
parameter menus
Allows for viewing the factory parameters
43
History
(current status)
Press Enter
to view history
of recent exceptions
Diagnostic Display
44
HF cable
(select)
Superuser Parameter
Select from 3-foot or 12-foot remote
45
Run Time