RVS-DX, Digital Soft Starter Instruction Manual—04/01/04
7-5
Start Up Procedure With Pump Control
Starting Curve
1. Adjust main parameters as necessary (FLA, FLC, etc).
2. Set Starting Curve, Acceleration Time, Current Limit, and Initial Voltage to their default values
(curve 0, 10 sec., 400% and 30% respectively).
3. Start the pump while watching the pressure gauge as the pump starts and look for overshooting
(“Pressure Surge”) of the gauge needle
above the target pressure. In case of over
pressure, choose a peak torque reduction
curve (Pump Control curve 1!).
4. Set Start Curve 1!, increase Acceleration
Time to 15 sec. and reduce Current Limit
to 350%. Start the pump and watch the
pressure gauge while the pump starts.
5. In most cases, overshooting is reduced, if
the overshoot persists, increase Acceleration time to 25 sec. (confirm with motor manufacturer)
and try again.
6. If the overpressure persists, increase Starting Curve setting to 2!, or 3!, if necessary. Each
increase in Starting Curve setting will reduce the Peak Torque, thus, reducing the overpressure
and preventing the “Pressure Surge” during start.
7. To increase starting time above these maximums, employ “Extended Parameters Settings” (page
5-7).
Stopping Curve
1. Adjust main parameters as necessary (FLA, FLC, etc.)
2. Set Stop Curve and Deceleration Time, to their default values (curve 0, 10 sec., respectively).
3. Stop the pump, watching the pressure gauge and check valve as the pump stops. Look for
overshooting (“Water Hammer”) of the gauge
(abruptly stops the pump and the motor).
4. Select Stop Curve 1, increase Deceleration time
to 15 seconds. Stop the pump and watch the
pressure gauge and the rate of closing of the
check valve as the pump stops. Abrupt stopping
of the pump and motor will cause a loud audible
noise emitted from the check valve.
5. In most cases, “Water Hammer” is reduced. If the
“Water Hammer” persists, increase the time to 25
seconds (confirm with motor manufacturer) and try again.
6. If the “Water Hammer” persists, increase Stop Curve setting to 2!, or 3!. Each increase in stop
curve will reduce the abrupt stop of the pump, thus, preventing the “Water Hammer”
phenomenon.
Voltage
Pump control during
Summary of Contents for 188-10130
Page 7: ...c h a p t e r 1 Introduction...
Page 8: ...This page intentionally left blank...
Page 11: ...c h a p t e r 2 Installation...
Page 12: ...This page intentionally left blank...
Page 15: ...c h a p t e r 3 RVS DX Terminals and Wiring...
Page 16: ...This page intentionally left blank...
Page 18: ...RVS DX Digital Soft Starter Instruction Manual 04 01 04 3 4 Typical Wiring Diagram...
Page 21: ...c h a p t e r 4 Control Layout...
Page 22: ...This page intentionally left blank...
Page 27: ...c h a p t e r 5 Features...
Page 28: ...This page intentionally left blank...
Page 37: ...c h a p t e r 6 Parameters...
Page 38: ...This page intentionally left blank...
Page 46: ...c h a p t e r 7 Start Up Procedure...
Page 47: ...This page intentionally left blank...
Page 52: ...C h a p t e r 8 Troubleshooting...
Page 53: ...This page intentionally left blank...
Page 56: ...a p p e n d i x A Technical Data Specifications...
Page 57: ...This page intentionally left blank...
Page 60: ...a p p e n d i x B Dimensional Drawings...
Page 61: ...This page intentionally left blank...
Page 64: ...RVS DX Digital Soft Starter Instruction Manual 4 01 04 B 5 Protected Chassis RVS DX 210 310A...
Page 65: ...a p p e n d i x C Fuse Selection Table...