RVS-DX, Digital Soft Starter Instruction Manual—4/01/04
5-3
Start/Stop Features
The RVS-DX incorporates many features that assist in starting and/or stopping various applications.
These features are described within this section.
Pump Control (Start Curves)
Induction motors produce peak torque up to three times the rated torque. This peak torque can occur
towards the end of the starting process. In pump applications, this peak torque may cause high
pressure in the pipes.
The RVS-DX incorporates four different starting curves. The start curve (curve 0) is the standard
curve and the default. It is the most stable and suitable curve for the motor, preventing prolonged
starting and motor overheating. Pump start curves (1, 2, and 3) automatically control the voltage
ramp-up to reduce peak torque. The multiple starting curves are shown below:
NOTE:
Always start with Start curve 0. If towards end of acceleration, peak torque is too high,
proceed to curve 1, then 2 and 3 if necessary.
Tach Feedback (0-10 VDC)
The tach feedback provides linear acceleration and deceleration curves according to RPM feedback.
Twelve tachometer gain levels can be selected for closed loop control for starting and stopping.
NOTE:
Always begin with minimum gain (0) and proceed with higher gain levels if required.
Pulse Start
The pulse start feature is used to break away high friction loads. High friction loads may require
close to across the line starting torque for a very short duration of time. The pulse start feature
accomplishes this with an 80% voltage boost (without current limit) for a period of 0.1 to 1 second.
After this pulse, the voltage is ramped down to the initial voltage setting where it begins ramping up
again to full voltage.
Voltage
Torque
DOL
0
1
2
3
Speed
Time
Summary of Contents for 188-10130
Page 7: ...c h a p t e r 1 Introduction...
Page 8: ...This page intentionally left blank...
Page 11: ...c h a p t e r 2 Installation...
Page 12: ...This page intentionally left blank...
Page 15: ...c h a p t e r 3 RVS DX Terminals and Wiring...
Page 16: ...This page intentionally left blank...
Page 18: ...RVS DX Digital Soft Starter Instruction Manual 04 01 04 3 4 Typical Wiring Diagram...
Page 21: ...c h a p t e r 4 Control Layout...
Page 22: ...This page intentionally left blank...
Page 27: ...c h a p t e r 5 Features...
Page 28: ...This page intentionally left blank...
Page 37: ...c h a p t e r 6 Parameters...
Page 38: ...This page intentionally left blank...
Page 46: ...c h a p t e r 7 Start Up Procedure...
Page 47: ...This page intentionally left blank...
Page 52: ...C h a p t e r 8 Troubleshooting...
Page 53: ...This page intentionally left blank...
Page 56: ...a p p e n d i x A Technical Data Specifications...
Page 57: ...This page intentionally left blank...
Page 60: ...a p p e n d i x B Dimensional Drawings...
Page 61: ...This page intentionally left blank...
Page 64: ...RVS DX Digital Soft Starter Instruction Manual 4 01 04 B 5 Protected Chassis RVS DX 210 310A...
Page 65: ...a p p e n d i x C Fuse Selection Table...