MAGICFX FLAMEBLAZER
®
—
User and Installation Manual
33
Inspect and clean
nozzles.
Remove nozzle with FLAMEBLAZER Nozzle exchange tool.
Submerge nozzle in Isopropanol for minimum of 1 minute.
Remove from solution and when dry use compressed air to
blow through the nozzle in opposite direction of fuel. Before
inserting nozzle back into machine conduct a visual check of
the washer seal to make sure no damage to the soft material
and replace the washer seal if damaged.
Inspect and clean
spark ignition
probes.
Any foreign particles should be removed from the probes,
which can be cleaned with Isopropanol and a light abrasive
cloth. Ignition probes should not be adjusted from the factory
setting as this is critical to safe and reliable ignition. To check
they are in the correct position each pair of probes must have
a gap from tip to tip of 4 mm (+/-2 mm) and opposite probes
must have a gap from tip to tip of 16 mm (+2 mm). If they do
not have these gaps or are miss-aligned in anyway contact
MAGIC FX.
Contact MAGIC FX if the FLAMEBLAZER is not functioning correctly.
Firmware updates can add additional features and fix bugs so regulalry check on
the website or with your MAGIC FX account manager to ensure you have the latest
version.