4.0 - MANUAL RESET
To reset the shut-off valve:
• Close the flow downstream of the valve in order to balance the pressure between upstream and downstream when opening.
DN 20 ÷ DN 50 P.max 1 - 6 bar:
(see fig. 1 and 4)
• Unscrew the reset knob and protection (
1
), turn it over and tighten the threaded hole “
A
” to the reset pin (
14
);
• Pull the reset knob (
1
) upwards and wait a few seconds for the pressure upstream and downstream of the valve to stabilise.
Next pull the reset knob upwards (
1
) until it hooks;
• Retighten the knob (
1
) to the initial position.
DN 65 ÷ DN 150 P.max 1 bar:
(see fig. 2)
• Pull the reset knob (
1
) upwards and wait a few seconds for the pressure upstream and downstream of the valve to stabilise;
• Next pull the reset knob upwards (
1
) until it hooks;
DN 65 ÷ DN 150 P.max 6 bar:
(see fig. 3 and 5)
• Completely unscrew and remove the reset knob (
1
);
• Screw the threaded hole “
B
” of the knob (
1
) onto the threaded end of the reset pin (
17
);
• Press the knob (
1
) assembled with the pin (
17
) downward and screw it onto the central pin (
18
);
• Pull the reset knob (
1
) upwards and wait a few seconds for the pressure upstream and downstream of the valve to stabilise;
Next pull the reset knob upwards (
1
) until it hooks;
• Blocking the pin (
17
) unscrew the reset knob (
1
);
• IMPORTANT:
completely unscrew the reset pin (
17
) from the pin (
18
);
• Tighten the knob (
1
) in the original position.
NOTE (for all versions):
If during the first reset attempt the valve remains open, try to increase the calibration value of the
block pressure, tightening the OPSO adjustment screw a few turns (
11
), after this repeat the reset procedure.
3.4 - GENERIC EXAMPLE OF AN INSTALLATION
1. M16/RM N.C. Manual reset solenoid valve
2. SM jerk ON/OFF valve
3. FM gas filter
4. OPSO series MVB/1 MAX shut off valve
5. RG/2MC pressure regulator
6. MVS/1 relief valve
7. Pressure gauge and relative button
8. Vent valve
9. Ball valve
10. Gas detector
11. SM remote jerk ON/OFF valve lever control
12. Expansion joint/anti-vibration mount
1
2
3
4
5
6
8
9
7
7
10
11
piping
application
discharge in open air
internal thermal unit
non-hazardous ventilated zone*
external roof
12
* if the zone is ATEX classified follow the indications of 3.3
5 DN