2.0 TECHNICAL NOTES
2.a) INPUTS AP(6) / CH(7)
the contacts to insert in these two inputs are free of tension (n.a.), aP input makes the bollard goes down, CH
input raises the bollard.
INPUT AP(6)
It is possible to connect in parallel to this entry the following devices:
- n.a. Button
- emergency vehicles sound recognizer (sirens, police, ambulance, etc.)
- access control: telepass, reading plate, magnetic coil, ecc.
INPUT CH(7)
It is possible to connect in parallel to this input the following devices::
- n.a. Button
- Clock contact (optional hardware) (activate the programming)
2.b) SIC1+2 SAFETY INPUT F2(4)
It has been projected for the input of any safety device (even if they are connected in series).
this input allows the reversal of running direction (only if the bollard is closing the passage).
Devices connectable to this input:
-magnetic detector with single/double coil.
-active modulated infrared photocells.
-Pre-calibrated pressure switch
-Positive opening limit switch installed under the sensitive head.
-any devices that respect the current laws
2.c) OUTPUTS
Specific circuit for the ignition of an engine to improve the performances of the bollard (prevention against
malfunctions, route defusing, ex. glued contacts).
2.d) TRAFFIC LIGHTS (16-17-18)
It has been projected to ensure a safe passage of the vehicle in the passage protected by the bollard. the green
light will appear when the passage will be free from any obstacle.
2.e) ELECTRICAL VALVE (17-18)
It has been projected to guarantee the passage even in case of power failure.
the electrical valve will make the bollard go down up to the ground level.
2.f) OUTPUT 24V (13-14)
It is used for the power supply of the auxiliary devices (ex. Photocells).
2.g) LED LIGHTS SENSITIVE HEAD 24F (13-15)
It has been projected to supply 1 flashing bright head.
2.h) INSTALLATION
- the control board must be installed in a protected and dry place with its own protection box.
- Install a circuit breaker of type 0,03a, high sensitivity to the supply of the control board.
- make sure the supply of the control board is 230Vac ±10% 50Hz.
- For the control board, electrical motor, flashing light, traffic lights, electrical valve; use cables with wire not less
than 1,5mm ² up to 50m of distance; for limit switches and accessories of command and safety use cables with
wires of 1mm ². for distances of more than 50 meters use the appropriate wires with the suitable section for the
installation. note: for applications such as lights, cameras etc. use static relays.
- The installation should be made by competent staff and in compliance with the legislation in force
- Before starting the installation, verify the integrity of the control board.
- the installation, the electrical connections and the regulations must be done to the letter.
- Packaging materials (cardboard, plastic, polystyrene, etc.) should not be dispersed into the environment.
- Do not install the control board in environment exposed to danger or disturbed by electro-magnetic fields. The
presence of gas or flammable smokes is a great danger for safety.
- Provide on the supply network a protection for extra tensions, a switch/ disconnecting switch and/or differential
fit for the product and with the current law.
- the constructor declines every responsibility if other devices and/or components incompatible with the product
for integrity are installed, safety and functioning of the product.
- for reparation or substitution, only original spare parts must be used.
- the installer must give all the information related to the functioning, maintenance and use of the single parts
and of the system in its entireness following the Directive machine (see laws en 12635, en 12453 and en
12445).