73
SC100/200 Series Function Block Application Manual EM-6460-C
■
CODING LIST ESSENTIALS
GROUP
ITEM
DATA
FUNCTION
30
10
11
9 2
9
Counter block
Count set to ‘9’
72
10
6 9
Program setter block
81
10
9 5
Sequential control block
11
12
13
14
1 3 0 0 0 1
1 0 7 2 0 2
1 0 3 0 0 1
0 2 8 0 0 5
ST
OF
OF
NI
STEP 01
G72 - 02 PRG hold SW OFF
G30 - 01 Counter run SW OFF
G80 - 05 System’s internal SW S5 OFF
15
16
17
18
19
20
21
1 3 0 0 0 2
0 9 7 2 0 2
0 9 3 0 0 1
0 1 8 0 0 5
0 7 3 0 0 2
0 1 3 0 1 1
1 2 0 0 0 1
ST
ON
ON
IN
OT
IN
BR
STEP 02
G72 - 02 PRG hold SW ON
G30 - 01 Counter run SW ON
G80 - 05 System’s internal SW S5 ON
G30 - 02 Counter pulse input SW ON
G30 - 11 Counter complete status ON
BR 01 Branch to STEP 01
STEP 01
System’s Internal SW
Program Running
SW S5 OFF
• S2 Program hold SW OFF
• S1 Counter run SW OFF
STEP 02
Count Complete
Program Halted
Y1 Count ‘Complete’ status ON
• S2 Program hold SW ON
• S1 Counter run SW ON
• Counter pulse input
Branch to STEP 01
STEP 01
STEP 02