EM-7814  Rev.3  P. 14 / 18

 

MAXIMUM / MINIMUM VALUE

RGTR.

ID

PARAMETER

UNIT

Circuit 1

Circuit 2

769

2769

I MAX

Current MAX

mA

771

2771

U MAX

Voltage MAX

V/100

773

2773

P MAX

Active power MAX

W

775

2775

Q MAX

Reactive power MAX

var

777

2777

S MAX

Apparent power MAX

VA

779

2779

PF MAX

Power factor MAX

1/10 000

781

2781

F MAX

Frequency MAX

Hz/100

801
803
805

2801
2803
2805

I1 MAX
I2 MAX
I3 MAX

Current MAX, Line 1
Current MAX, Line 2
Current MAX, Line 3

mA
mA
mA

807

2807

IN MAX

Neutral current MAX

mA

809
811
813

2809
2811
2813

U12 MAX
U23 MAX
U31 MAX

Delta voltage MAX, 1 – 2
Delta voltage MAX, 2 – 3
Delta voltage MAX, 3 – 1

V/100
V/100
V/100

815
817
819

2815
2817
2819

U1N MAX
U2N MAX
U3N MAX

Phase voltage MAX, Phase 1
Phase voltage MAX, Phase 2
Phase voltage MAX, Phase 3

V/100
V/100
V/100

821
823
825

2821
2823
2825

P1 MAX
P2 MAX
P3 MAX

Active power MAX, Phase 1
Active power MAX, Phase 2
Active power MAX, Phase 3

W
W
W

827
829
831

2827
2829
2831

Q1 MAX
Q2 MAX
Q3 MAX

Reactive power MAX, Phase 1
Reactive power MAX, Phase 2
Reactive power MAX, Phase 3

var
var
var

833
835
837

2833
2835
2837

S1 MAX
S2 MAX
S3 MAX

Apparent power MAX, Phase 1
Apparent power MAX, Phase 2
Apparent power MAX, Phase 3

VA
VA
VA

839
841
843

2839
2841
2843

PF1 MAX
PF2 MAX
PF3 MAX

Power factor MAX, Phase 1
Power factor MAX, Phase 2
Power factor MAX, Phase 3

1/10 000
1/10 000
1/10 000

865
867
869

2865
2867
2869

THD I1 MAX
THD I2 MAX
THD I3 MAX

Current total harmonic distortion MAX, Line 1
Current total harmonic distortion MAX, Line 2
Current total harmonic distortion MAX, Line 3

%/10
%/10
%/10

871

2871

THD IN MAX

Neutral current total harmonic distortion MAX

%/10

873
875
877

2873
2875
2877

THD U12 MAX
THD U23 MAX
THD U31 MAX

Delta voltage total harmonic distortion MAX, 1 – 2
Delta voltage total harmonic distortion MAX, 2 – 3
Delta voltage total harmonic distortion MAX, 3 – 1

%/10
%/10
%/10

879
881
883

2879
2881
2883

THD U1N MAX
THD U2N MAX
THD U3N MAX

Phase voltage total harmonic distortion MAX, Phase 1
Phase voltage total harmonic distortion MAX, Phase 2
Phase voltage total harmonic distortion MAX, Phase 3

%/10
%/10
%/10

897

2897

I MAX AVG

Current MAX AVG

mA

899
901
903

2899
2901
2903

I1 MAX AVG
I2 MAX AVG
I3 MAX AVG

Current MAX AVG, Line 1
Current MAX AVG, Line 2
Current MAX AVG, Line 3

mA
mA
mA

905

2905

IN MAX AVG

Neutral current MAX AVG

mA

907
909

2907
2909

P MAX AVG+
P MAX AVG–

Active power MAX AVG, incoming
Active power MAX AVG, outgoing

W
W

911
913

2911
2913

Q MAX AVG+
Q MAX AVG–

Reactive power MAX AVG, incoming
Reactive power MAX AVG, outgoing

var
var

915

2915

S MAX AVG

Apparent power MAX AVG

VA

929

2929

I  MIN

Current MIN

mA

931

2931

U MIN

Voltage MIN

V/100

933

2933

P MIN

Active power MIN

W

935

2935

Q MIN

Reactive power MIN

var

937

2937

S MIN

Apparent power MIN

VA

939

2939

PF MIN

Power factor MIN

1/10 000

941

2941

F MIN

Frequency MIN

Hz/100

961
963
965

2961
2963
2965

I1 MIN
I2 MIN
I3 MIN

Current MIN, Line 1
Current MIN, Line 2
Current MIN, Line 3

mA
mA
mA

967

2967

IN MIN

Neutral current MIN

mA

Summary of Contents for R7CWTU

Page 1: ...ATIONAL RANGE Locate the power input rating marked on the product and confirm its operational range as indicated below 100 240V AC rating 85 264V 50 60 Hz 8VA 110 240V DC rating 99 264V 3W GENERAL PRECAUTIONS Before you remove or mount the unit turn off the power supply and input signal for safety DO NOT set the switches on the module while the power is supplied The switches are used only for main...

Page 2: ... address Factory setting 00 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 9 8 7 6 Station Address Setting x1 Station Address Setting x10 BAUD RATE Baud Rate is selected with the rotary switch Factory setting 0 156 kbps 5 4 3 2 1 0 9 8 7 6 Baud Rate Setting 0 156 kbps 1 625 kbps 2 2 5 Mbps 3 5 Mbps 4 10 Mbps OPERATING MODE SETTING Factory setting System Configuration SW1 1 1 2 SW1 1 SW1 2 SYSTEM CONFIGURATION OF...

Page 3: ...2K 2ch current input 2K 9 2ch 3L 2ch current input 3L 18 2ch 3K 2ch current input 3K PIN No ID FUNCTION PIN No FUNCTION ID PIN No ID FUNCTION PIN No FUNCTION ID STATUS INDICATOR LED PWR RUN ERR SD 1 RD STATUS 2 ON ON BL BL ON Communicates normally with occasional CRC errors due to noise interference ON ON BL BL ON Communicates normally but the Baud Rate and or Station Address switches failed ERR L...

Page 4: ... M3 SCREW TERMINALS for Voltage Current Discrete Input 6 24 6 24 CONNECTION DIAGRAM VOLTAGE INPUT CURRENT INPUT DISCRETE INPUT Di 1 COM COM Di 2 Di 3 Di 4 Discrete input connection e g 1 5 10 2 6 4 7 13 8 9 14 12 15 11 16 17 18 P1 TO OTHER CC Link DEVICES P3 N 1L 2L 3L DI 2 DI 4 COM NC COM NC 1K 2K 3K DI 1 DI 3 P2 3 4 1 2 5 3 DA DB DG SLD FG 6 7 1 5 10 2 6 4 7 13 8 9 14 12 15 11 16 17 18 P1 P3 N 1...

Page 5: ...e load u v v u U V V U k l K L P1 P2 P3 1K 1L L1 source load L2 L3 k l K L P1 P2 1K 1L L1 source load N k l K L u v U V P1 P2 1K 1L L1 source load N k l K L System Application Single phase 2 wire Three phase 3 wire balanced load Note Use CLSE for CT Grounding is unnecessary for low voltage circuit Single phase 3 wire Three phase 3 wire unbalanced load 2CT Terminal System Application Terminal L1 L2...

Page 6: ...s in the unit via CC Link accord ing to the tables below All registers are composed of two words in signed integer Negative values are in two s complements Refer to CC Link OPERATIONS in this manual for register numbers and their contents Master to Slave R7CWTU Bit data RY0 Set ON in order to execute the command Set OFF after RX0 turns ON RY1 Command 0 Reading 1 Writing Word data RWw0 Register num...

Page 7: ...er Register number RWr2 Data to write LSW RWr3 Data to write MSW Sequence 3 Following the completion of a command the unit sets reply data in RWr2 and RWr3 and sets RX0 ON Slave R7CWTU to Master REPLY READING WRITING RX0 ON ON RWr1 Error code Error code RWr2 Data to read LSW RWr3 Data to read MSW Error Codes ERROR CODE COMMAND CONTENTS 100H Reading No error 111H Command error 112H Device error Tim...

Page 8: ...0 when the resetting procedure is complete after one of these values is written at this address If another value is written before 0 has been set the former resetting procedure ends indefinitely Specific values can be preset to each register by writing at this address from the host 5331 Reboot system Write 10001 to reboot the system Any other values can be written but invalid 5332 Backup restore s...

Page 9: ...E R5 1 CLSE 05 2 CLSE 10 3 CLSE 20 4 CLSE 40 5 CLSE 60 6 Reserved 7 Reserved 5604 VT rating Primary 0 to 400 000 Voltage V Factory setting 110 V 5606 VT rating Secondary 50 to 500 Voltage V Factory setting 110 The secondary can be set up to 500V However this does not mean the unit accepts 500V for input Do not use with the condition exceeding input rating written in the specification sheet of the ...

Page 10: ...AMETER 5987 Power factor PF1 through PF3 PF sign 0 Standard IEC Identical to the active energy 1 Special type 1 IEEE Positive in LAG Negative in LEAD 5988 Reactive power Q1 through Q3 Q sign 0 Standard IEC Positive from PF 1 0 to 180 in LAG direction Negative for the other direction 1 Special type 1 Positive in LAG Negative in LEAD 5989 Reactive power Q1 through Q3 calculation Q Q1 Q2 Q3 0 Standar...

Page 11: ...ID PARAMETER UNIT Circuit 1 Circuit 2 1 4001 I Current mA 3 4003 U Voltage V 100 5 4005 P Active power W 7 4007 Q Reactive power var 9 4009 S Apparent power VA 11 4011 PF Power factor 1 10 000 13 4013 F Frequency Hz 100 15 4015 DIR Phase difference direction 0 inductive or lag 1 capacitive or lead 33 35 37 4033 4035 4037 I1 I2 I3 Current Line 1 Current Line 2 Current Line 3 mA mA mA 39 4039 IN Neu...

Page 12: ...ctive energy low tariff incoming outgoing kvarh 10 193 4193 EP_L Active energy fraction high tariff incoming kWh 10 232 195 4195 EQ_L Reactive energy fraction high tariff LAG kvarh 10 232 197 4197 ES_L Apparent energy fraction high tariff kVAh 10 232 199 4199 EP _L Active energy fraction high tariff outgoing kWh 10 232 201 4201 EQ _L Reactive energy fraction high tariff LEAD kvarh 10 232 203 205 4...

Page 13: ...09 311 4307 4309 4311 I1 AVG 3 I2 AVG 3 I3 AVG 3 Current AVG Line 1 History 3 Current AVG Line 2 History 3 Current AVG Line 3 History 3 mA mA mA 313 4313 IN AVG 3 Neutral current AVG History 3 mA 321 4321 I AVG 4 Current AVG History 4 mA 323 325 327 4323 4325 4327 I1 AVG 4 I2 AVG 4 I3 AVG 4 Current AVG Line 1 History 4 Current AVG Line 2 History 4 Current AVG Line 3 History 4 mA mA mA 329 4329 IN ...

Page 14: ...se 3 1 10 000 1 10 000 1 10 000 865 867 869 2865 2867 2869 THD I1 MAX THD I2 MAX THD I3 MAX Current total harmonic distortion MAX Line 1 Current total harmonic distortion MAX Line 2 Current total harmonic distortion MAX Line 3 10 10 10 871 2871 THD IN MAX Neutral current total harmonic distortion MAX 10 873 875 877 2873 2875 2877 THD U12 MAX THD U23 MAX THD U31 MAX Delta voltage total harmonic dis...

Page 15: ...N S2 MIN S3 MIN Apparent power MIN Phase 1 Apparent power MIN Phase 2 Apparent power MIN Phase 3 VA VA VA 999 1001 1003 2999 3001 3003 PF1 MIN PF2 MIN PF3 MIN Power factor MIN Phase 1 Power factor MIN Phase 2 Power factor MIN Phase 3 1 10 000 1 10 000 1 10 000 TOTAL HARMONIC DISTORTION THD RGTR ID PARAMETER UNIT Circuit 1 Circuit 2 1281 1283 1285 8281 8283 8285 THD I1 THD I2 THD I3 Current total h...

Page 16: ...4th id 5th id 6th id 7th id 8th id 9th id 10th id 11th id 12th id 13th id 14th id 15th id 16th id 17th id 18th id 19th id 20th id 21st id 22nd id 23rd id 24th id 25th id 26th id 27th id 28th id 29th id 30th id 31st 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 1601 1630 8601 8630 HD I2 2 HD I2 31 Current harmonic Line 2 2nd 31st 10 1665 1694 8665 8694 HD...

Page 17: ...added at 999 999 999 counts 3143 Discrete input 4 count Pulse train input at Discrete input 4 is counted The counter resets to 0 when a pulse is added at 999 999 999 counts DEVICE STATUS RGTR PARAMETER 8001 Input overload Bit assignment as shown below 15 Bit 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 U1N I1 U2N I2 I3 U3N U12 U23 U31 F I1 2 I2 2 I3 2 1 is placed at the bit where an overload is detected I3 ...

Page 18: ...1st 9608 4th 3rd 9609 6th 5th 9610 8th 7th 9611 10th 9th 9612 12th 11th 9613 14th 13th 9614 16th 15th 9623 Extension function flag Reading the following values depending upon the function 0002H RS 485 Modbus RTU 0010H Three phase 4 wire system 0080H LONWORKS 0100H CC Link 2000H Modbus TCP This register is read as follows depending upon model numbers R7LWTU 0090H 144 R7CWTU 0110H 272 R7MWTU 0012H 1...

Reviews: