DEVICE INFORMATION
RGTR.
PARAMETER
9601
Device ID
7701 : R7xWTU
9602
Device version
Version number × 100 (e.g. Version 1.00 = 100)
9603
Serial No.
Each character is stored in the following address:
Register
Upper Byte
Lower Byte
9603
2nd
1st
9604
4th
3rd
9605
6th
5th
9606
8th
7th
9607
Tag name
This register is writable.
Each character is stored in the following address:
Register
Upper Byte
Lower Byte
9607
2nd
1st
9608
4th
3rd
9609
6th
5th
9610
8th
7th
9611
10th
9th
9612
12th
11th
9613
14th
13th
9614
16th
15th
9623
Extension function flag
Reading the following values depending upon the function:
0002H : RS-485 (Modbus RTU)
0010H : Three-phase / 4-wire system
0080H : L
ON
W
ORKS
0100H : CC-Link
2000H : Modbus/TCP
This register is read as follows depending upon model numbers.
R7LWTU : 0090H (144)
R7CWTU : 0110H (272)
R7MWTU : 0012H (18)
R7EWTU : 2010H (8208)
9627
Number of circuits
1 : 1 circuit (R7xWTU-211-AD4)
2 : 2 circuits (R7xWTU-221-AD4)
9628
Number of counters
0 : None (R7xWTU-221-AD4)
4 : 4 points (R7xWTU-211-AD4)
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.