DISCRETE INPUT
RGTR.
PARAMETER
3073
Discrete input 1 status
0 : OFF
1 : ON
3074
Discrete input 2 status
0 : OFF
1 : ON
3075
Discrete input 3 status
0 : OFF
1 : ON
3076
Discrete input 4 status
0 : OFF
1 : ON
■
DISCRETE INPUT COUNT
RGTR.
PARAMETER
3137
Discrete input 1 count
Pulse train input at Discrete input 1 is counted.
The counter resets to 0 when a pulse is added at 999 999 999 counts.
3138
Discrete input 2 count
Pulse train input at Discrete input 2 is counted.
The counter resets to 0 when a pulse is added at 999 999 999 counts.
3141
Discrete input 3 count
Pulse train input at Discrete input 3 is counted.
The counter resets to 0 when a pulse is added at 999 999 999 counts.
3143
Discrete input 4 count
Pulse train input at Discrete input 4 is counted.
The counter resets to 0 when a pulse is added at 999 999 999 counts.
■
DEVICE STATUS
RGTR.
PARAMETER
8001
Input overload
Bit assignment as shown below.
15
Bit
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
U1N
I1
U2N
I2
I3
U3N
U12
U23
U31
F
I1.2
I2.2
I3.2
‘1’ is placed at the bit where an overload is detected.
I3.2, I2.2 and I1.2 are assigned to current values for Circuit 2.
8002
Reserved
8003
System error
Bit assignment as shown below.
15
Bit
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
STAT AVG ENE SET FDT PRG
PRG : Control software error
FDT : Factory calibration data error
SET : User setting data error
ENE : Energy data error
AVG : Average data error
STAT : Maximum / minimum data error
‘1’ is placed when the respective errors are detected. All measuring operations stop while one or more sys-
tem errors are detected.
■
DIAGNOSTICS
RGTR.
PARAMETER
UNIT
9217
Processing delays
times
9219
Processing delay sequence number
No.