R7CWTU
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-7814 Rev.3 P. 3 / 18
■
POWER SUPPLY, CC-Link TERMINAL ASSIGNMENT
4
DA
5
DG
6
U(+)
1
DB
2
SLD
3
FG
7
V(−)
1. DB
White
2. SLD
Shield
3. FG
FG
4. DA
Blue
5. DG
Yellow
6. U(+)
Power input (+)
7. V(−)
Power input (−)
■
INPUT TERMINAL ASSIGNMENT
•
1 Circuit, 4 point discrete
14
5
6
2K
2L
3L
15
3K
16
17
18
7
8
9
DI1
+
DI3
+
COM
DI2
+
DI4
+
10
1
2
P3
P1
P2
11
NC
12
13
3
4
1ch
1ch
1ch
1ch
1ch
1ch
NC
1K
N
1L
COM
1
P1
Voltage Input P1
10
P3
Voltage Input P3
2
P2
Voltage Input P2
11
NC
Unused
3
N
Voltage Input N
12
NC
Unused
4
1ch 1L 1ch current input 1L
13 1ch 1K 1ch current input 1K
5
1ch 2L 1ch current input 2L
14 1ch 2K 1ch current input 2K
6
1ch 3L 1ch current input 3L
15 1ch 3K 1ch current input 3K
7
DI2 +
Discrete input 2
16 DI1 +
Discrete input 1
8
DI4 +
Discrete input 4
17 DI3 +
Discrete input 3
9
COM Discrete input common
18
COM Discrete input common
• 2 Circuits
14
5
6
2K
2L
3L
15
3K
16
17
18
7
8
9
10
1
2
P3
P1
P2
11
NC
12
13
3
4
1ch
1ch
1ch
1ch
1ch
1ch
NC
1K
N
1L
2K
2L
3L
3K
2ch
2ch
2ch
2ch
2ch
2ch
1K
1L
1
P1
Voltage Input P1
10
P3
Voltage Input P3
2
P2
Voltage Input P2
11
NC
Unused
3
N
Voltage Input N
12
NC
Unused
4
1ch 1L 1ch current input 1L
13 1ch 1K 1ch current input 1K
5
1ch 2L 1ch current input 2L
14 1ch 2K 1ch current input 2K
6
1ch 3L 1ch current input 3L
15 1ch 3K 1ch current input 3K
7
2ch 1L 2ch current input 1L
16 2ch 1K 2ch current input 1K
8
2ch 2L 2ch current input 2L
17 2ch 2K 2ch current input 2K
9
2ch 3L 2ch current input 3L
18 2ch 3K 2ch current input 3K
PIN
No.
ID
FUNCTION
PIN
No.
FUNCTION
ID
PIN
No.
ID
FUNCTION
PIN
No.
FUNCTION
ID
STATUS INDICATOR LED
PWR
RUN
ERR
SD
*
1
RD
STATUS
*
2
ON
ON
BL
BL
ON
Communicates normally with occasional CRC errors due to noise interference.
ON
ON
BL
BL
ON
Communicates normally but the Baud Rate and/or Station Address switches failed.
ERR LED blinks approximately in 0.5 seconds intervals.
ON
ON
BL
BL
OFF
----
ON
ON
BL
OFF
ON
CRC error found in the received data. Unable to respond.
ON
ON
BL
OFF
OFF
----
ON
ON
OFF
BL
ON
Normal communication
ON
ON
OFF
BL
OFF
----
ON
ON
OFF
OFF
ON
Unable to receive data addressed to the station.
ON
ON
OFF
OFF
OFF
----
ON
OFF
BL
BL
ON
Performs the interval-timed responses but CRC error found in receiving the refresh
data.
ON
OFF
BL
BL
OFF
----
ON
OFF
BL
OFF
ON
CRC error found in the data addressed to the station.
ON
OFF
BL
OFF
OFF
----
ON
OFF
OFF
BL
ON
Link is not started.
ON
OFF
OFF
BL
OFF
----
ON
OFF
OFF
OFF
ON
No data addressed to the station. Or unable to receive data addressed to the sta-
tion due to noise interference. (Missing parts of the data sent from the master)
ON
OFF
OFF
OFF
OFF
Unable to receive data due to wire breakdown
ON
OFF
ON
OFF
ON/OFF Faulty Baud Rate and/or Station Address setting
BL
OFF
OFF
OFF
OFF
Blinking in approx. 0.5 Hz intervals: Input overload or no input
Blinking in approx. 2 Hz intervals: Setting error or device error
OFF
OFF
OFF
OFF
OFF
Power input removed. Or power supply failure.
OFF = OFF, ON = ON, BL = Blinking
*1. SD LED may look not blinking but ON with high baud rate and fewer connected modules.
*2. LEDs indicated with “----” in STATUS rarely occurs in normal operation (LED failure or the like as possible cause).