CC-Link - MEASURED VARIABLES
Each measured variable has different engineering unit (Refer to the table below). For example, when 40000 is read at the
register 41 for the 1 – 2 delta voltage, the actual voltage value equals to 400.0V = 40000 × 0.01, as the engineering unit for
this item is V/100 (0.01V).
Readable range for each parameter depends upon the parameter type, as shown in the table below. For example, Current
unit is applied to Line current or Neutral current, and Voltage unit is applied to the 1 – 2 delta voltage or the minimum value
voltage.
TYPE
UNIT
RANGE
Current
mA
0 to 2 000 000 000 mA
Voltage
V/100
0 to 20 000 000.00 V
Active power
W
-2 000 000 000 to 2 000 000 000 W
Reactive power
var
-2 000 000 000 to 2 000 000 000 var
Apparent power
VA
0 to 2 000 000 000 VA
Power factor
1/10 000
-1.0000 to 1.0000
Frequency
Hz/100
0 or 40.00 Hz to 70.00 Hz
Active energy
kWh/10
0 to 99 999 999.9 kWh *
1
Reactive energy
kvarh/10
0 to 99 999 999.9 kvarh *
1
Apparent energy
kVAh/10
0 to 99 999 999.9 kVAh *
1
Energy count time
h/10
0 to 99 999 999.9 hours *
1
Harmonic distortion
%/10
0 to 999.9 %
Phase angle between phase voltages
°
-180 to +180°
*1. Reset to 0 at overflow
■
MOMENTARY VALUE
RGTR.
ID
PARAMETER
UNIT
Circuit 1
Circuit 2
1
4001
I
Current
mA
3
4003
U
Voltage
V/100
5
4005
P
Active power
W
7
4007
Q
Reactive power
var
9
4009
S
Apparent power
VA
11
4011
PF
Power factor
1/10 000
13
4013
F
Frequency
Hz/100
15
4015
DIR
Phase difference direction (0 = inductive or lag, 1 = capacitive or lead)
---
33
35
37
4033
4035
4037
I1
I2
I3
Current, Line 1
Current, Line 2
Current, Line 3
mA
mA
mA
39
4039
IN
Neutral current
mA
41
43
45
4041
4043
4045
U12
U23
U31
Delta voltage, 1 – 2
Delta voltage, 2 – 3
Delta voltage, 3 – 1
V/100
V/100
V/100
47
49
51
4047
4049
4051
U1N
U2N
U3N
Phase voltage, Phase 1
Phase voltage, Phase 2
Phase voltage, Phase 3
V/100
V/100
V/100
53
55
57
4053
4055
4057
P1
P2
P3
Active power, Phase 1
Active power, Phase 2
Active power, Phase 3
W
W
W
59
61
63
4059
4061
4063
Q1
Q2
Q3
Reactive power, Phase 1
Reactive power, Phase 2
Reactive power, Phase 3
var
var
var
65
67
69
4065
4067
4069
S1
S2
S3
Apparent power, Phase 1
Apparent power, Phase 2
Apparent power, Phase 3
VA
VA
VA
71
73
75
4071
4073
4075
PF1
PF2
PF3
Power factor, Phase 1
Power factor, Phase 2
Power factor, Phase 3
1/10 000
1/10 000
1/10 000
77
79
81
4077
4079
4081
DIR1
DIR2
DIR3
Phase difference direction, Phase 1 (0 = inductive or lag, 1 = capacitive or lead)
Phase difference direction, Phase 2 (0 = inductive or lag, 1 = capacitive or lead)
Phase difference direction, Phase 3 (0 = inductive or lag, 1 = capacitive or lead)
---
---
---
83
85
87
4083
4085
4087
UT12
UT23
UT31
Phase angle between Phase 1 – 2 voltages
Phase angle between Phase 2 – 3 voltages
Phase angle between Phase 3 – 1 voltages
°
°
°