R7K4FML3-6-DAC32B

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-7773-E  Rev.3  P. 2 / 11

COMPONENT IDENTIFICATION

4

5

6

7

1

2

3

28 29 30 31

20 21 22

19

33 34 35 36

25 26 27

24

32

23

10 11 12 13

2

3

4

1

15 16 17 18

7

8

9

6

14

5

1

SA1

×10

SA2

×1

2 3 4

ON

PWR

LNK2

CON

LNK1

ERR

LNK1

LNK2

MECHATROLINK

Connector

Station Address Setting

Rotary SW

Status Indicator LED

Operating Mode Setting DIP SW (SW1)

Discrete I/O Status Indicator LED

Power Supply Terminals

I/O Terminals

 

STATUS INDICATOR LED

ID

COLOR

FUNCTION

PWR

Green

Turns on when the internal power 
is supplied normally.

ERR

Red

Turns on at MECHATROLINK-III 
communication error

CON

Green

Turns on at MECHATROLINK-III 
connection is established

LNK1

Green

Turns on at MECHATROLINK-III 
LNK1 is established

LNK2

Green

Turns on at MECHATROLINK-III 
LNK2 is established

 

STATION ADDRESS

Station Address is selected between 03H and EFH in hexa-
decimal.
The SA1 switch determines the MSD, while the SA2 switch 
does the LSD of the address.
(Factory setting: 03H)

Station Address Setting (LSD)

Station Address Setting (MSD)

89A

BC

D

EF

0123

45

67

89A

BC

D

EF

0123

45

67

 

OPERATING MODE

(*) Factory setting

• Read Rate (SW1-1, 1-2, 1-3)

SW1-1

SW1-2

SW1-3

READ RATE

OFF

OFF

OFF

≤ 10 msec. (*)

ON

OFF

OFF

≤ 1 msec.

OFF

ON

OFF

≤ 5 msec.

ON

ON

OFF

≤ 20 msec.

OFF

OFF

ON

≤ 50 msec.

ON

OFF

ON

≤ 70 msec.

OFF

ON

ON

≤ 100 msec.

ON

ON

ON

≤ 200 msec.

• Output at The Loss of Communication (SW1-4)

SW1-4

OUTPUT AT THE LOSS OF COMMUNICATION

OFF

Reset the output (turned off)

ON

Hold the output (*)
(maintains the last data received normally)

 

DISCRETE I/O STATUS INDICATOR LED

LED green indicators shows the signal status.
  ON  : LED ON
  OFF : LED OFF

 

POWER SUPPLY TERMINAL ASSIGNMENT

4

NC

5

6

7

1

2

3

NC

+

24V

0V

NC

NC

FE

1. NC
2. NC
3. FE
4. NC
5. NC
6. +24V
7. 0V

-
-
Functional earth
-
-
Power supply (24V DC)
Power supply  (0V)

 POWER SUPPLY TERMINAL ASSIGNMENT

Summary of Contents for MECHATROLINK R7K4FML3-6-DAC32B

Page 1: ...on the product and confirm its operational range as indicated below 24V DC rating 24V 10 100mA GENERAL PRECAUTIONS Before you remove the unit or mount it turn off the power supply and I O signal for s...

Page 2: ...on at MECHATROLINK III LNK2 is established STATION ADDRESS Station Address is selected between 03H and EFH in hexa decimal The SA1 switch determines the MSD while the SA2 switch does the LSD of the a...

Page 3: ...0 29 Y1 30 31 21 22 Y3 Y5 Y2 Y4 Y14 NO ID FUNCTION NO ID FUNCTION 19 V Out Common 28 V External excitation 20 Y0 Output 0 29 Y1 Output 1 21 Y2 Output 2 30 Y3 Output 3 22 Y4 Output 4 31 Y5 Output 5 23...

Page 4: ...IONS Connect the unit as in the diagram below EXTERNAL DIMENSIONS unit mm inch DIN RAIL 35mm wide 4 16 50 1 97 3 5 14 5 2 210 8 27 220 8 66 235 9 25 47 1 85 45 1 77 6 36 M3 SCREW TERMINALS FOR I O 6 7...

Page 5: ...n 1 10 X0 COM X15 NPN Connection 1 10 X0 COM X15 COM COM 19 23 28 20 24 22 25 31 26 27 32 30 33 29 34 35 36 21 V V Y18 Y20 Y22 Y24 Y26 Y28 Y30 Y17 Y31 Y19 Y21 Y23 Y25 Y27 Y29 Y16 2 18 Output Connectio...

Page 6: ...or warning command ALM_CLR 06H Clear alarm or warning command CONNECT 0EH Establish connection command DISCONNECT 0FH Release connection command Standard I O profile DATA_RWA 20H Transmit I O data NOP...

Page 7: ...CMD_STAT 3 4 0000H 0000H Clear current alarm or warning Other than 0000H is not available 5 6 00H 00H Reserve CONNECT 0EH Starts communication with master station BYTE COMMAND RESPONSE REMARKS 0 CONN...

Page 8: ...ent from the slave to the master are set in the response With output data read back CH0 IN LO CH0 data low 8 bits Bit 0 through 7 of input data are set CH0 IN HI CH0 data high 8 bits Bit 8 through 15...

Page 9: ...LO CH2 data low 8 bits Not used CH2 OUT HI CH2 data high 8 bits Not used CH3 OUT LO CH3 data low 8 bits Not used CH3 OUT HI CH3 data high 8 bits Not used CMD_CTRL CMD_CTRL command area is following BI...

Page 10: ...125 sec 17H Max Transmission Cycle 4 Yes 0x0061A800 64 msec 18H Increments of Transmission Cycle 4 Yes 0x00000001 Available to 31 25 62 5 125 250 500 sec 1 64 msec 1 msec increments 19H Min Communica...

Page 11: ...N Phone 81 6 6659 8201 Fax 81 6 6659 8510 E mail info m system co jp EM 7773 E Rev 3 P 11 11 I O DATA DESCRIPTION DISCRETE I O MODULE 0 15 Input 0 Input 1 Input 2 Input 3 Input 15 0 OFF 1 ON Input 7 I...

Reviews: