EM-3608 Rev.9 P. 4 / 9
■
DEFAULT PARAMETER SETTING
Param.
Block
Name
Default setting Unit
Programmable range
Explanations of function
1*
3
ST1
100.0
Engineering unit*
6
-5 to +105 % FS
Alarm setpoint value SET1
ST2
0.0
Engineering unit*
6
-5 to +105 % FS
Alarm setpoint value SET2
PTn
1
N/A
1, 2, 3
Display pattern
2*
4
HYS1
1.0
Deviative engineering unit*
6
0 to 102 % FS
Deadband (hysteresis) for SET1
HYS2
1.0
Deviative engineering unit*
6
0 to 102 % FS
Deadband (hysteresis) for SET2
P-SL
0.0
Engineering unit*
6
-1999 to 9999
Scaling, lower range
P-SU
100.0
Engineering unit*
6
-1999 to 9999
Scaling, upper range
P-dP
1
N/A
0, 1, 2*
7
Decimal point position
P-A1
1
N/A
0 to 8
Alarm mode for SET1
P-A2
2
N/A
0 to 8
Alarm mode for SET2
bUrn
H
N/A
H, L
Burnout protection
(upscale or downscale)
P-d1
1
Seconds
1 to 10
Switching delay timer for SET1
P-d2
1
Seconds
1 to 10
Switching delay timer for SET2
3*
5
P-dF
5.0
Seconds
0.0 to 900.0
Time constant for the input filter
ADJ0
0.0
Deviative engineering unit*
6
-50 to +50 % FS
User’s ZERO adjustment
ADJS
0.0
Deviative engineering unit*
6
-50 to +50 % FS
User’s SPAN adjustment
P-d0
0
Seconds
0 to 20
Power ON delay time
REST
OFF
ON/OFF*
8
Resetting parameter
Ver
X.XX
Firmware version
*3. Pressing SEL key for 3 seconds turn the unit into setting mode for Parameter block 1.
*4. Pressing SEL key for 7 seconds turn the unit into setting mode for Parameter block 2.
*5. Pressing SEL key for 9 seconds turn the unit into setting mode for Parameter block 3.
*6. Parameters set with “Engineering unit” or “Deviative engineering unit” shift according to changes in P-SL or P-SU setting
regardless of the setting with ordering information sheet.
*7. 0 for no decimal point position, 1 for one-place decimal, 2 for two-place decimal.
*8. 3 sec. after REST to ON or by pressing SEL key, “Resetting parameter” is performed to reset parameters to default settings
regardless of the setting with ordering information sheet.