COMPONENT IDENTIFICATION

A. Measured Value (PV) / 

Alarm SET1 Display

B. Measured Value (PV)

Indicator LED

D. SELECT Key

C. Alarm SET2 / Parameter Display

J. Alarm SET2 Indicator LED

H. Alarm SET1 Indicator LED

G. Power Indicator LED

F. DOWN Key

E. UP Key

Ref.

Component Name

Function

A

Measured Value (PV) / Alarm SET1 Display Displaying either of Measured Value (PV) or Alarm Setpoint Value (SET1)

B

Measured Value (PV) Indicator LED

LED turns on when the Measured Value (PV) is displayed.

C

Alarm SET2 / Parameter Display

Displaying either of Alarm Setpoint Value (SET2) or parameter type code.

D

SELECT Key

Used for confirming current setpoints and switching between parameter 
blocks.

E

UP Key

Pressing the key increases display values.
They change continuously when it is kept pressed.

F

DOWN Key

Pressing the key decreases display values.
They change continuously when it is kept pressed.

G

Power Indicator LED

LED turns on while the power is turned on.

H

Alarm SET1 Indicator LED

LED turns on when the Alarm SET1 is in tripped conditions.

I

Alarm SET2 Indicator LED

LED turns on when the Alarm SET2 is in tripped conditions.

PREPARING POWER-UP

When the power is turned on, the unit displays all segments 
on the Measured Value (PV)/Alarm Setpoint Value (SET1) 
Display and on the Alarm Setpoint Value (SET2)/Parameter 
Display before starting operation.
To ensure a proper operation of the unit, set the parameters 
before starting up according to the operating conditions.
Be sure to remove power of the final control element before 
parameters setting.
Wait for 10 minutes for warming up the unit before its tem-
perature is stabilized and measuring is started.

HOW TO SET PARAMETERS

 

CONFIRMING CURRENT MEASURED VALUE AND 

ALARM SETPOINT VALUES

Pressing SEL key turns the display in order of SET1, SET2, 
PV, and blank.

Key

Status or Operation

Display

Current display
(PTn = 1 in this example)*

2

Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)

SEL

Press the key once.

Display pattern 2
Upper = PV (value)
Lower = blank

SEL

Press the key once.

Display pattern 3
Upper = blank
Lower = blank

SEL

Press the key once.

Returning to Display 
pattern 1

*2.  Which display pattern is to be displayed first after the 

power is turned on can be programmed in Parameter block 
1.

 

REGISTERING SETTING

1) Data is registered automatically in 3 seconds after the 

data is set.  Pressing SEL key also register the data.

2) The display automatically returns to the display pattern 

preset by PTn parameter when the unit is left for approx. 

30 seconds with no access.

Summary of Contents for KS2V2

Page 1: ...ture change or condensation Corrosive gases sulfide and ammonia in particular or flammable gases Vibration or mechanical shock Direct contact with water oil chemical materials steam or vapor Exposure...

Page 2: ...6 CONNECTION DIAGRAM 7 8 10 11 9 2 3 1 N C N O COM SET1 N C N O COM SET2 U V POWER INPUT 5 6 PANEL CUTOUT unit mm 45 45 0 5 0 0 5 0 85 MIN 63 MIN INSTALLATION Detach the yellow clamps located at the t...

Page 3: ...ET2 is in tripped conditions PREPARING POWER UP When the power is turned on the unit displays all segments on the Measured Value PV Alarm Setpoint Value SET1 Display and on the Alarm Setpoint Value SE...

Page 4: ...Switching delay timer for SET1 P d2 1 Seconds 1 to 10 Switching delay timer for SET2 3 5 P dF 5 0 Seconds 0 0 to 900 0 Time constant for the input filter ADJ0 0 0 Deviative engineering unit 6 50 to 50...

Page 5: ...Pat tern 2 Pattern 3 Upper blank Lower ST1 DOWN Press the key once Next parameter name is displayed Upper black Lower ST2 SEL Press the key once ST2 is replaced with current setting Upper blank Lower...

Page 6: ...tus or Operation Display Current display PTn 2 in this example Display pattern 2 Upper PV Lower blank SEL Keep pressing the key for 7 seconds Maintain while the display indicates Pat tern 2 Pattern 3...

Page 7: ...Upper ST1 setpoint Lower ST2 setpoint SEL Keep pressing the key for 7 seconds Upper blank Maintain while the display indicates Pat tern 2 Pattern 3 and Parameter block 1 until HYS1 is on the display L...

Page 8: ...ame ADJ0 again Upper blank Lower ADJ0 SEL Keep pressing the key for 3 seconds Maintain while the display changes Display pattern 1 Upper ST1 setpoint Lower ST2 setpoint User s SPAN adjustment Example...

Page 9: ...Low alarm With the function the unit is NOT tripped until the input goes once above and then below the setpoint ERROR MESSAGES DISPLAY ERROR DESCRIPTION WHAT TO DO UUUU The input exceeds 105 Return th...

Reviews: