HOW TO SET PARAMETER BLOCK 3

Press SEL key for 9 seconds until the display turns to the 
setting mode for Parameter block 3.

Time constant for the input filter
[Example]

 Changing time constant for the input filter (P-

dF) from 5.0 sec. to 10.0 sec.

Key

Status or Operation

Display

Current display
(PTn = 1 in this example)

Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)

SEL

Keep pressing the key for 9 seconds.

Maintain while the display indicates Pat-

tern 2, Pattern 3, and Parameter block 1, 2, 
until P-dF is on the display.

Upper = blank
Lower = P-dF

SEL

Press the key once.

P-dF is replaced with current setting.

Upper = blank
Lower = 5.0

UP

DOWN

Press the keys until the display indicates 10.0.
(New value is registered if the unit is not 
accessed for 3 seconds.)

Upper = blank
Lower = 10.0

SEL

Press the key once.

The lower display indicates the param-

eter name (P-dF) again.

Upper = blank
Lower = P-dF

SEL

Keep pressing the key for 3 seconds.

Maintain while the display changes.

Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)

User’s ZERO adjustment
[Example]

Calibrate display value with 0% input (ADJ0) from 2 to 0.
ADJ0:  0 

 -2

Key

Status or Operation

Display

Current display
(PTn = 1 in this example)

Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)

SEL

Keep pressing the key for 9 seconds.

Maintain while the display indicates Pat-

tern 2, Pattern 3, and Parameter block 1, 2, 
until P-dF is on the display.

Upper = blank
Lower = P-dF

DOWN Press the key twice.

Next parameter name is displayed.

Upper = blank
Lower = ADJ0

SEL

Press the key once.

ADJ0 is replaced with current setting.

Upper = blank
Lower = 0

UP

DOWN

Press the keys until the display indicates -2.
(New value is registered if the unit is not 
accessed for 3 sec.)

Upper = blank
Lower = -2

SEL

Press the key once.

The lower display indicates the param-

eter name (ADJ0) again.

Upper = blank
Lower = ADJ0

SEL

Keep pressing the key for 3 seconds.

Maintain while the display changes.

Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)

User’s SPAN adjustment
[Example]

 Calibrate display value with 100% input (ADJS) 

from 99 to 100.
ADJS:   0 

 1

Key

Status or Operation

Display

Current display
(PTn = 1 in this example)

Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)

SEL

Keep pressing the key for 9 seconds.

Maintain while the display indicates Pat-

tern 2, Pattern 3, and Parameter block 1, 2, 
until P-dF is on the display.

Upper = blank
Lower = P-dF

DOWN Press the key three times.

Next parameter name is displayed.

Upper = blank
Lower = ADJS

SEL

Press the key once.

ADJS is replaced with current setting.

Upper = blank
Lower = 0

UP

DOWN

Press the keys until the display indicates 1.
(New value is registered if the unit is not 
accessed for 3 sec.)

Upper = blank
Lower = 1

SEL

Press the key once.

The lower display indicates the param-

eter name (ADJS) again.

Upper = blank
Lower = ADJS

SEL

Keep pressing the key for 3 seconds.

Maintain while the display changes.

Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)

Power ON delay time (P-d0)
[Example]

Changing power ON delay time (the time interval for the 
alarm outputs to be enabled after the power is turned on.) 
from 0 sec. to 3 sec.

Key

Status or Operation

Display

Current display
(PTn = 1 in this example)

Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)

SEL

Keep pressing the key for 9 seconds.

Maintain while the display indicates Pat-

tern 2, Pattern 3, and Parameter block 1, 2, 
until P-dF is on the display.

Upper = blank
Lower = P-dF

DOWN Press the key four times.

Next parameter name is displayed.

Upper = blank
Lower = P-d0

SEL

Press the key once.

P-d0 is replaced with current setting.

Upper = blank
Lower = 0

UP

DOWN

Press the keys until the display indicates 3.
(New value is registered if the unit is not 
accessed for 3 sec.)

Upper = blank
Lower = 3

SEL

Press the key once.

The lower display indicates the param-

eter name (P-d0) again.

Upper = blank
Lower = P-d0

SEL

Keep pressing the key for 3 seconds.

Maintain while the display changes.

Display pattern 1
Upper = ST1 (setpoint)
Lower = ST2 (setpoint)

Summary of Contents for KS2V2

Page 1: ...ture change or condensation Corrosive gases sulfide and ammonia in particular or flammable gases Vibration or mechanical shock Direct contact with water oil chemical materials steam or vapor Exposure...

Page 2: ...6 CONNECTION DIAGRAM 7 8 10 11 9 2 3 1 N C N O COM SET1 N C N O COM SET2 U V POWER INPUT 5 6 PANEL CUTOUT unit mm 45 45 0 5 0 0 5 0 85 MIN 63 MIN INSTALLATION Detach the yellow clamps located at the t...

Page 3: ...ET2 is in tripped conditions PREPARING POWER UP When the power is turned on the unit displays all segments on the Measured Value PV Alarm Setpoint Value SET1 Display and on the Alarm Setpoint Value SE...

Page 4: ...Switching delay timer for SET1 P d2 1 Seconds 1 to 10 Switching delay timer for SET2 3 5 P dF 5 0 Seconds 0 0 to 900 0 Time constant for the input filter ADJ0 0 0 Deviative engineering unit 6 50 to 50...

Page 5: ...Pat tern 2 Pattern 3 Upper blank Lower ST1 DOWN Press the key once Next parameter name is displayed Upper black Lower ST2 SEL Press the key once ST2 is replaced with current setting Upper blank Lower...

Page 6: ...tus or Operation Display Current display PTn 2 in this example Display pattern 2 Upper PV Lower blank SEL Keep pressing the key for 7 seconds Maintain while the display indicates Pat tern 2 Pattern 3...

Page 7: ...Upper ST1 setpoint Lower ST2 setpoint SEL Keep pressing the key for 7 seconds Upper blank Maintain while the display indicates Pat tern 2 Pattern 3 and Parameter block 1 until HYS1 is on the display L...

Page 8: ...ame ADJ0 again Upper blank Lower ADJ0 SEL Keep pressing the key for 3 seconds Maintain while the display changes Display pattern 1 Upper ST1 setpoint Lower ST2 setpoint User s SPAN adjustment Example...

Page 9: ...Low alarm With the function the unit is NOT tripped until the input goes once above and then below the setpoint ERROR MESSAGES DISPLAY ERROR DESCRIPTION WHAT TO DO UUUU The input exceeds 105 Return th...

Reviews: