background image

KS2V2

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-3608  Rev.9  P. 6 / 9

 

HOW TO SET PARAMETER BLOCK 2

Press SEL key for 7 seconds until the display turns to the setting mode for Parameter block 2.

Deadband (hysteresis) for SET1
[Example]

Changing deadband (hysteresis) (HYS1) for SET1 from 1 to 5.

Key

Status or Operation

Display

Current display
(PTn = 3 in this example)

Display pattern 3
Upper = blank
Lower = blank

SEL

Keep pressing the key for 7 seconds.

Maintain while the display indicates 

Pattern 2, Pattern 3, and Parameter block 
1, until HYS1 is on the display.

Upper = blank
Lower = HYS1

SEL

Press the key once.  

HYS1 is replaced with current seting.

Upper = blank
Lower = 1

UP

Press the keys until the display indicates 
5.

Upper = blank

DOWN (New value is registered if the unit is not 

accessed for 3 sec.)

Lower = 5

SEL

Press the key once.

The lower display indicates the param-

eter name (HYS1) again.

Upper = blank
Lower = HYS1

SEL

Keep pressing the key for 3 seconds.

Maintain while the display changes.

Display pattern 3
Upper = blank
Lower = blank

Deadband (hysteresis) for SET2
[Example]

Changing deadband (hysteresis) (HYS2) for SET2 from 1 to 3.

Key

Status or Operation

Display

Current display
(PTn = 3 in this example)

Display pattern 3
Upper = blank
Lower = blank

SEL

Keep pressing the key for 7 seconds.

Maintain while the display indicates Pat-

tern 2, Pattern 3, and Parameter block 1, 
until HYS1 is on the display.

Upper = blank
Lower = HYS1

DOWN Press the key once.

Next parameter name is displayed.

Upper = blank
Lower = HYS2

SEL

Press the key once.

HYS2 is replaced with current setting.

Upper = blank
Lower = 1

UP

DOWN

Press the keys until the display indicates 3.
(New value is registered if the unit is not 
accessed for 3 sec.)

Upper = blank
Lower = 3

SEL

Press the key once.

The lower display indicates the param-

eter name (HYS2) again.

Upper = blank
Lower = HYS2

SEL

Keep pressing the key for 3 seconds.

Maintain while the display changes.

Display pattern 3
Upper = blank
Lower = blank

Scaling (P-SL, P-SU)
[Example]

Changing scale (input range) from 0 – 400 to -100 – 200.

Key

Status or Operation

Display

Current display
(PTn = 2 in this example)

Display pattern 2
Upper = PV
Lower = blank

SEL

Keep pressing the key for 7 seconds.

Maintain while the display indicates Pat-

tern 2, Pattern 3, and Parameter block 1, 
until HYS1 is on the display.

Upper = blank
Lower = HYS1

DOWN Press the key two times.

Next parameter name is displayed.

Upper = blank
Lower = P-SL

SEL

Press the key once.

P-SL is replaced with current setting.

Upper = blank
Lower = 0

UP

DOWN

Press the keys until the display indicates 
-100. (New value is registered if the unit is 
not accessed for 3 sec.)

Upper = blank
Lower = -100

SEL

Press the key once.

The lower display indicates the param-

eter name (P-SL) again.

Upper = blank
Lower = P-SL

DOWN Press the key once.

Next parameter name is displayed.

Upper = blank
Lower = P-SU

SEL

Press the key once.

P-SU is replaced with current setting.

Upper = blank
Lower = 400

UP

DOWN

Press the keys until the display indicates 200.
(New value is registered if the unit is not 
accessed for 3 sec.)

Upper = blank
Lower = 200

SEL

Press the key once.

The lower display indicates the param-

eter name (P-SU) again.

Upper = blank
Lower = P-SU

SEL

Keep pressing the key for 3 seconds.

Maintain while the display changes.

Display pattern 2
Upper = PV
Lower = blank

Decimal point position for the scaled range
[Example]

Changing decimal point position (P-dP) from XXX to XXX.X.

Key

Status or Operation

Display

Current display
(PTn = 2 in this example)

Display pattern 2
Upper = PV
Lower = blank

SEL

Keep pressing the key for 7 seconds.

Maintain while the display indicates Pat-

tern 2, Pattern 3, and Parameter block 1, 
until HYS1 is on the display.

Upper = blank
Lower = HYS1

DOWN Press the key four times.

Next parameter name is displayed.

Upper = blank
Lower = P-dP

SEL

Press the key once.

P-dP is replaced with current setting.

Upper = blank
Lower = 0

UP

DOWN

Press the keys until the display indicates 1.
(New value is registered if the unit is not 
accessed for 3 sec.)

Upper = blank
Lower = 1

SEL

Press the key once.

The lower display indicates the param-

eter name (P-dP) again.

Upper = blank
Lower = P-dP

SEL

Keep pressing the key for 3 seconds.

Maintain while the display changes.

Display pattern 2
Upper = PV
Lower = blank

 

SETPOINT v.s. DECIMAL POINT POSITION

Code

Decimal point position

Notes

0
1
2

XXXX
XXX.X
XX.XX

No decimal point
One-place decimal
Two-place decimal

Summary of Contents for KS2V2

Page 1: ...ture change or condensation Corrosive gases sulfide and ammonia in particular or flammable gases Vibration or mechanical shock Direct contact with water oil chemical materials steam or vapor Exposure...

Page 2: ...6 CONNECTION DIAGRAM 7 8 10 11 9 2 3 1 N C N O COM SET1 N C N O COM SET2 U V POWER INPUT 5 6 PANEL CUTOUT unit mm 45 45 0 5 0 0 5 0 85 MIN 63 MIN INSTALLATION Detach the yellow clamps located at the t...

Page 3: ...ET2 is in tripped conditions PREPARING POWER UP When the power is turned on the unit displays all segments on the Measured Value PV Alarm Setpoint Value SET1 Display and on the Alarm Setpoint Value SE...

Page 4: ...Switching delay timer for SET1 P d2 1 Seconds 1 to 10 Switching delay timer for SET2 3 5 P dF 5 0 Seconds 0 0 to 900 0 Time constant for the input filter ADJ0 0 0 Deviative engineering unit 6 50 to 50...

Page 5: ...Pat tern 2 Pattern 3 Upper blank Lower ST1 DOWN Press the key once Next parameter name is displayed Upper black Lower ST2 SEL Press the key once ST2 is replaced with current setting Upper blank Lower...

Page 6: ...tus or Operation Display Current display PTn 2 in this example Display pattern 2 Upper PV Lower blank SEL Keep pressing the key for 7 seconds Maintain while the display indicates Pat tern 2 Pattern 3...

Page 7: ...Upper ST1 setpoint Lower ST2 setpoint SEL Keep pressing the key for 7 seconds Upper blank Maintain while the display indicates Pat tern 2 Pattern 3 and Parameter block 1 until HYS1 is on the display L...

Page 8: ...ame ADJ0 again Upper blank Lower ADJ0 SEL Keep pressing the key for 3 seconds Maintain while the display changes Display pattern 1 Upper ST1 setpoint Lower ST2 setpoint User s SPAN adjustment Example...

Page 9: ...Low alarm With the function the unit is NOT tripped until the input goes once above and then below the setpoint ERROR MESSAGES DISPLAY ERROR DESCRIPTION WHAT TO DO UUUU The input exceeds 105 Return th...

Reviews: