HOW TO SET PARAMETER BLOCK 2
Press SEL key for 7 seconds until the display turns to the setting mode for Parameter block 2.
Deadband (hysteresis) for SET1
[Example]
Changing deadband (hysteresis) (HYS1) for SET1 from 1 to 5.
Key
Status or Operation
Display
Current display
(PTn = 3 in this example)
Display pattern 3
Upper = blank
Lower = blank
SEL
Keep pressing the key for 7 seconds.
→
Maintain while the display indicates
Pattern 2, Pattern 3, and Parameter block
1, until HYS1 is on the display.
Upper = blank
Lower = HYS1
SEL
Press the key once.
→
HYS1 is replaced with current seting.
Upper = blank
Lower = 1
UP
Press the keys until the display indicates
5.
Upper = blank
DOWN (New value is registered if the unit is not
accessed for 3 sec.)
Lower = 5
SEL
Press the key once.
→
The lower display indicates the param-
eter name (HYS1) again.
Upper = blank
Lower = HYS1
SEL
Keep pressing the key for 3 seconds.
→
Maintain while the display changes.
Display pattern 3
Upper = blank
Lower = blank
Deadband (hysteresis) for SET2
[Example]
Changing deadband (hysteresis) (HYS2) for SET2 from 1 to 3.
Key
Status or Operation
Display
Current display
(PTn = 3 in this example)
Display pattern 3
Upper = blank
Lower = blank
SEL
Keep pressing the key for 7 seconds.
→
Maintain while the display indicates Pat-
tern 2, Pattern 3, and Parameter block 1,
until HYS1 is on the display.
Upper = blank
Lower = HYS1
DOWN Press the key once.
→
Next parameter name is displayed.
Upper = blank
Lower = HYS2
SEL
Press the key once.
→
HYS2 is replaced with current setting.
Upper = blank
Lower = 1
UP
DOWN
Press the keys until the display indicates 3.
(New value is registered if the unit is not
accessed for 3 sec.)
Upper = blank
Lower = 3
SEL
Press the key once.
→
The lower display indicates the param-
eter name (HYS2) again.
Upper = blank
Lower = HYS2
SEL
Keep pressing the key for 3 seconds.
→
Maintain while the display changes.
Display pattern 3
Upper = blank
Lower = blank
Scaling (P-SL, P-SU)
[Example]
Changing scale (input range) from 0 – 400 to -100 – 200.
Key
Status or Operation
Display
Current display
(PTn = 2 in this example)
Display pattern 2
Upper = PV
Lower = blank
SEL
Keep pressing the key for 7 seconds.
→
Maintain while the display indicates Pat-
tern 2, Pattern 3, and Parameter block 1,
until HYS1 is on the display.
Upper = blank
Lower = HYS1
DOWN Press the key two times.
→
Next parameter name is displayed.
Upper = blank
Lower = P-SL
SEL
Press the key once.
→
P-SL is replaced with current setting.
Upper = blank
Lower = 0
UP
DOWN
Press the keys until the display indicates
-100. (New value is registered if the unit is
not accessed for 3 sec.)
Upper = blank
Lower = -100
SEL
Press the key once.
→
The lower display indicates the param-
eter name (P-SL) again.
Upper = blank
Lower = P-SL
DOWN Press the key once.
→
Next parameter name is displayed.
Upper = blank
Lower = P-SU
SEL
Press the key once.
→
P-SU is replaced with current setting.
Upper = blank
Lower = 400
UP
DOWN
Press the keys until the display indicates 200.
(New value is registered if the unit is not
accessed for 3 sec.)
Upper = blank
Lower = 200
SEL
Press the key once.
→
The lower display indicates the param-
eter name (P-SU) again.
Upper = blank
Lower = P-SU
SEL
Keep pressing the key for 3 seconds.
→
Maintain while the display changes.
Display pattern 2
Upper = PV
Lower = blank
Decimal point position for the scaled range
[Example]
Changing decimal point position (P-dP) from XXX to XXX.X.
Key
Status or Operation
Display
Current display
(PTn = 2 in this example)
Display pattern 2
Upper = PV
Lower = blank
SEL
Keep pressing the key for 7 seconds.
→
Maintain while the display indicates Pat-
tern 2, Pattern 3, and Parameter block 1,
until HYS1 is on the display.
Upper = blank
Lower = HYS1
DOWN Press the key four times.
→
Next parameter name is displayed.
Upper = blank
Lower = P-dP
SEL
Press the key once.
→
P-dP is replaced with current setting.
Upper = blank
Lower = 0
UP
DOWN
Press the keys until the display indicates 1.
(New value is registered if the unit is not
accessed for 3 sec.)
Upper = blank
Lower = 1
SEL
Press the key once.
→
The lower display indicates the param-
eter name (P-dP) again.
Upper = blank
Lower = P-dP
SEL
Keep pressing the key for 3 seconds.
→
Maintain while the display changes.
Display pattern 2
Upper = PV
Lower = blank
■
SETPOINT v.s. DECIMAL POINT POSITION
Code
Decimal point position
Notes
0
1
2
XXXX
XXX.X
XX.XX
No decimal point
One-place decimal
Two-place decimal