JC-IO USERS MANUAL EM-9044-B
1.5 Specifications
Table 2. Specfications
ITEM
DESCRIPTION
REMARKS
Power
24
V DC
Clock
RTC
Year(4 digits). month. date. day. hour.
minute. second
Configuration
Web server
PC configurator software (JCIOCFG)
Both are avilable to configurate all
parameters
Communication port
Ethernet 10 / 100 BASE-T
Communication for setting
Moduler jack RS-232-C
COP-US (required separately)
RUN contact
ON during operation (WTD)
OFF at detecting CPU abnormally
Indicator
Status indicator LED
POWER, RUN, COM, ERROR
Communication protocol
TCP/IP
ICMP
DHCP Client
SNTP Client
HTTP Client
Modbus/TCP Client
SLMP Client
Table 3. Related Products
ITEM
MODEL
PC configurator cable
MCN-CON or COP-US
PC configurator software
JCIOCFG
Table 4. General Specifications
ITEM
DESCRIPTION
Power supply, RUN contact output
Tension clamp terminal (Front Twin connection)
Unit side connector: MSTB2,5/5-GF-5,08AU
Cable side connector: TFKC2,5/5-STF-5,08AU
(Applicable wire size: 0.2 - 2.5 mm
2
, stripped length 10 mm)
Recommended solderless terminal
AI0,25-10YE 0.25 mm
2
(Phoenix Contact)
AI0,34-10TQ 0.34 mm
2
(Phoenix Contact)
AI0,5-10WH 0.5 mm
2
(Phoenix Contact)
AI0,75-10GY 0.75 mm
2
(Phoenix Contact)
AI1-10RD 1.0 mm
2
(Phoenix Contact)
AI1,5-10BK 1.5 mm
2
(Phoenix Contact)
AI2,5-10BU 2.5 mm
2
(Phoenix Contact)
Ethernet
RJ-45 connector
Housing material
Flame-resistant resin (gray)
Isolation
Ethernet to power supply to RUN contact output to FE
Calender clock
Year(4 digits). month. date. day. hour. minute. second
Status Indicator LED
POWER, RUN, COM, ERROR
RUN contact output
Photo MOSFET relay (no polarity); (OFF in CPU error detected)
•Peak load voltage: 50 V max.
•Continuous load current: 50 mA max.
•Peak load current: 300 mA max. (≤0.1 sec.)