40
JC-IO USERS MANUAL EM-9044-B
7.5 SLMP (client)
PROBLEM FACED
CHECKS TO BE DONE
METHOD OF HANDLING
Unnable to connect to
the SLMP device from
the JC-IO.
Is the LAN cable breakdown or dis-
connected from the HUB.
Connect the LAN cable securely.
Check the connecting LED of the HUB.
Has the IP address been set by manu-
ally?
Set the IP address manually.
(Refer to 4.3.2 Network Setting)
Has the same network address been
specified in the IP address of the JC-
IO and SLMP device?
Check the network address.
[Example]
JC-IO: 192.168.0.1
PC: 192.168.0.2
Subnet mask: 255.255.255.0
Are the IP address of the server de-
vice registered by JCIOCFG and the
IP address of the JC-IO same?
Check the IP address.
Refer to 4.4.3 C (Connection))
Is the IP address set to the SLMP
device?
Enable the server function of the SLMP
device.