JC-IO USERS MANUAL EM-9044-B
4.4.6 S (16-bit)
Figure 11.
Select S
★★★
Select S0 to S255.
Right-click to copy
and paste only
when the setting
values are normal.
Possible to paste
the setting values
copied by "Paste
(+1)" with the
effective register
and device number
increased by 1.
S (16-bit) Setting Screen
Table 23. S (16-bit) Setting Parameters
ITEM
DESCRIPTION
Mode
Enable / Disable S register.
Following parameters are configurable when Enable is selected.
CH name / CH comment
Enter the CH name and comment of S register in 32 characters or less.
Data type
Select SHORT / USHORT.
(Use to set manually from web server)
Input
Connection
Select from C0 to C31 or L0 to L255
Register
Modbus/TCP
When C is selected to Connection and the protocol is set to
Modbus/TCP, set the input register. When the unit identifier
is set to variable, set the unit identification number.
SLMP
When C is selected to Connection and the protocol is set to
SLMP, set the input device.
The display format for device address can be switched
between octal, decimal, and hexadecimal.
Word
When L is selected for the Connection,supecify Upper /Lower.
Upper: Upper 16-bit data of L register
Lower: Lower 16-bit data of L register
Output
Connection
Select from C0 to C31 or disabled.
Following parameters are configurable when Cx is selected.
Register
Modbus/TCP
When the protocol of the specified Connection is set to
Modbus/TCP, set the output register. When the unit identifier
is set to variable, set the unit identification number.
SLMP
When the protocol of the specified Connection is set to
SLMP, set the output device.
The display format for device address can be switched
between octal, decimal, and hexadecimal.