4.4.3 C (Connection)
Set the Connection on this screen.
Refer to 3.1 Connection for details of the Connection.
Figure 9.
Select C
Select C0 to C31.
Right-click to copy
and paste only
when the setting
values are normal.
C (Connection) Setting Screen
Table 21. C (Connection) Setting Parameters
ITEM
DESCRIPTION
Mode
Enable / Disable Connection.
Following parameters are configurable when Enable is selected.
CH name / CH comment
Enter the CH name and comment in 32 characters or less.
Protocol
Select Modbus/TCP or SLMP.
IP address
Set the IP address of the connecting device.
Port address
Set the connecting port address from 0 to 65535.
Sampling rate
Set the sampling rate of the Connection from 0 to 30000 (msec.).
Timeout
Set the communication timeout from 1 to 60 (sec.)
Modbus/TCP
Unit Identifier
Select Fixed / Variable.
When Fixed is seleced, set the common unit identifier to Connection.
When Variable is selected, set the unit identifier individually for each
internal register.
Refer to 3.4 Modbus/TCP
SLMP
Network No.
Set the network No. of the programable controller.
Station No.
Set the station No. of the programable controller.
Processor No.
Set the processor no. of the programmable controller in the hexa-
decimal number from 0x0000 to 0xFFFF.
Type
Select the sub-command type of SLMP from 16-bits or 32-bits.
Refer to 3.5 SLMP