background image

 

14 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

The recommended order of installation is as follows: 

1 – Familiarize yourself with this manual. 
2 – Check the minimum installation dimensions and vent installation. 
3 – Check your local installation codes. 
4 – Check you have the parts and components necessary to complete the installation. 
5 – Check the gas and electrical supplies are ready. 
6 – Prepare opening (remove any loose materials) 
7 – Install Venting 
8 – Install base unit and connect vent 
9 – Connect gas and electrical supplies. 
10 – Install operational components and prepared for first test fire 
11 – Check to verify adequate accessibility clearance for service & proper operation 
12 – Check operation of unit 
13 – Take time to explain operation to customer (most call backs are caused by the customer not understanding the operation 
of the unit.) 

 

Existing Gas Supply 

Before interrupting the existing gas supply it is recommended that the following be checked. 
Shut down all gas appliances and carry out a pressure test to ensure there are no leaks in the system. 
Before connecting the appliance to the gas supply line, double check that the appliance you have purchased is designed for the 
gas type you are using.  The gas type markings are located on the certification label and also on the appliance’s gas valve. 
Check the gas pressure immediately upstream to ensure you will be able to supply the minimum inlet pressure for the 
appliance. 
Check your pipe sizing to ensure sufficient volume will be supplied to the appliance. 
 

 

Gas Supply Installation 

Provide adequate clearance for the proper installation and checking of the gas connection. 
Have your gas supplier or a qualified gas fitter run a gas supply line into the gas fireplace.  The line must be properly sized 
and fitted according to the installation codes.  Upstream of the appliance supply connection, the fitter shall provide an easily 
accessible manual shut-off valve. 
The gas supply pipe should enter the appliance case through the opening at the right side.  The supply pipe should be 
connected to the appliance gas inlet pipe situated at the right side of the control unit.  Supply line connection to the inlet pipe 
is 3/8 NPT. 
Use only new black iron or steel pipes or copper tubing if acceptable – check local codes. 
 

Note that in the USA copper tubing must be internally tinned for protection against sulfur compounds. 

Unions in gas should be of ground joint type.  Sealant used must be resistant to the action of all gas constituents including LP 
gas.  Sealant should be applied lightly to male threads to ensure excess sealant does not enter gas lines. 

 

Pressure testing the supply line for leaks 

The appliance and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure 
testing of the system at test pressures in excess of ½ psig (3.4kPa).  The appliance must be isolated from the gas supply piping 
system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test 
pressures equal to or less than ½ psig (3.5kPa).  Failure to do so will damage the appliance’s gas valve.  Such damage is not 
covered by the manufacturer’s warranty. 
 
When testing for leaks: 
Make sure that the appliance is turned off. 
Open the manual shut-off valve. 
Test for leaks by applying a liquid detergent or soap solution to all ball joints.  Bubbles forming indicate a gas leak.  
Correct any leak detected immediately. 

Never use an open flame to check for leaks. 

 

The pressure test point locations are built in to the regulator that controls the burner manifold pressure.  The correct pressure 
range is shown in the table in the specification section of this manual.  The pressure check should be made with the burner lit. 

See lighting instruction section for full operating details. 

 

Installation Planning 

Summary of Contents for Riviera-42

Page 1: ...uture reference Do not store or use gasoline or other Flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not t...

Page 2: ...omponents Page 10 Vent Installation Page 11 Vertical Venting Page 12 Horizontal Venting Page 13 Exterior Vent Clearances Page 14 Installation Planning Page 15 Installing Non Combustible Panels Page 16...

Page 3: ...uld have at least on fire extinguisher An approved Class A B C extinguisher should be mounted on the wall near an exit and close to the application but not so close that accessibility to the extinguis...

Page 4: ...raffic areas Nothing should ever be placed on or near the surface of the fireplace including the top of the unit Clothing or other flammable material should not be placed on or near the appliance Make...

Page 5: ...g Electrical Rating 115 volts 0 7 amp 60hz Steady State Efficiency 67 45 P 4 1 Annual Fireplace Efficiency 56 50 Circulating fan optional Variable Speed Vent System Direct Vent Glass Ceramic Clean Fac...

Page 6: ...installed on the top of the opening Non combustible panel must be fastened to the top of any combustible framing 20 5 from floor or platform to the frame opening Is lowest acceptable measurement 24 t...

Page 7: ...to the ceiling must not be less than the 43 inches dictated by the internal ceiling height Mantel sizes and clearance when applicable follow guideline described in this manual Mantel Requirements No...

Page 8: ...to the appliance access to the gas compartment becomes limited A grounded 117volt AC line must be supplied to the appliance and wired into the electrical box which is fixed to the right hand side of t...

Page 9: ...ng a separate solid fuel burning appliance Side Wall Co Axial termination without Nailing Flange V58 Side Wall Co Axial termination with Nail Flange RVF58 Vertical Co Axial Termination Simpson DuraVen...

Page 10: ...supports such as metal strapping Generally every six feet is preferable Co Axial 2 ply flexible chimney liner must be secured to appliance with a minimum of three screws for both 5 exhaust and 8 air...

Page 11: ...be either horizontal or vertical in any combination that does not exceed the four elbow limit All venting configurations that fall into the hatch area must have the 3 hole ring intake restrictor See p...

Page 12: ...must have a minimum 4 foot rise Shortest run for Natural gas is one foot vertical and one foot horizontal Liquid Propane requires two 2 Feet minimum rise vertical one 1 foot horizontal Vinyl or Plast...

Page 13: ...9 Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance K 1 83m 3 above if within 10 horizontally Clearance to mechanical air supply inlet L 2 13...

Page 14: ...upply connection the fitter shall provide an easily accessible manual shut off valve The gas supply pipe should enter the appliance case through the opening at the right side The supply pipe should be...

Page 15: ...ed only to avoid confusion The large 42 x34 25 inch front panel utilizes the cutout for installation under the appliance The 14 x 3 must be installed at the top of the wall opening when venting is rou...

Page 16: ...for supporting the cover grille to be installed on completion A Power drill with Hex Nut driver should be used to attach surround as shown in Figure 2 Pre punched holes are provided Once the top has...

Page 17: ...o secure it in place The Non combustible board can be fastened with standard drywall screws through the recessed holes provided when the appliance is ready to close in Figure 5 Figure 6 Install metal...

Page 18: ...ce Do not use substitute materials Replacement of the panel should only be carried out by a licensed qualified service person Door Removal and Re Installation Instructions Window Re Installation To Re...

Page 19: ...rical Schematic This appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 or the Canadi...

Page 20: ...stat to lowest setting or on off switch to off 2 Turn off all electrical power to the appliance 3 Remove control access 4 Remove backup batteries if service is to be performed or for extended shutdown...

Page 21: ...g s control and is not covered under warranty 1 Clean the glass regularly as soon as you notice the buildup white film If the film is left for a longer period of time build up will bake on Once baked...

Page 22: ...tch MUST be rated for electronic Minimize splicing in all wiring and solder all unavoidable splices Thermostat Wire Information AWG mm ft m 22 0 6 10 3 0 20 0 8 25 7 6 18 1 0 40 12 2 16 1 3 64 19 5 14...

Page 23: ...on glass Adjustment None Close damper Open damper Flame Quality Adjustment Access to this feature is done through the top of the burner cover by removing the two fasteners from the rectangular metal c...

Page 24: ...ifice Danna Controls LPPO Main Burner Orifice Liquid Propane MB042LP Main Burner Orifice Natural Gas MBO42NG NON COMBUSTABILE COMPONENTS Front Panel 43 X 34 w Base Panel for under Riviera 42 FB001 Thr...

Page 25: ...ponent Servicing Burner Removal First step is to remove the door Assembly refer to page 17 Once the door has been removed remove any decorative media that may be on the burner trays The rear baffle pa...

Page 26: ...with respect to the Luxor Limited Lifetime Warranty CFHMfg may at its discretion fully discharge all obligations with respect to this warranty by refunding to the original warranted purchaser the whol...

Reviews: