Framing and Clearances For Clean Face Fireplace (no louvers)
Note: Make sure that you allow for installation of any wiring, such
as the fan, remote control or wall switch before applying finishing
material.
The following diagram shows a typical framed installation. All clearances
must be adhered to. combustible material such as timber must not be
placed any closer to the appliance than the stand-offs allow.
Maintain required clearance around the vent pipe (1” horizontal 1” vertical).
Combustible material: Such as wood, compressed paper, plant fibers,
plastics or any material capable of igniting and burning, whether flame
proofed or not, plaster or un-plastered.
Framing the enclosure
It is best to frame your fireplace after it is positioned
and the system is installed. Framing dimensions are
as follows:
Model
MB-36
Depth
16”
Height
32”
Width
36”
B. Width
28”
Note: The Fireplace does not require a hearth
extension and may sit directly on combustible
materials.
Corner installation
Page 5
Inside framed size for termination:
-Luxor horizontal with flex: 10” x 10” inside
-Simpson DuraVent (P/N 984) 10” x 11”
Please note: Wall thimble (P/N 942) may be
required for installations in Canada.
58½”
41¼”
W
H
D
WARNING: No materials,
combustible or otherwise
shall occupy the space shown
surrounding unit.
Mantle clearances
3½”
Drywall
¾” mantle
12” mantle
2”x 4”
1”
4
½
”
Non combustible
*Unit to 3/4” trim is 8”
12”
8” mantle
10”
8”
Clean Face Kit
Please Note: The standoffs
provided with each MB-36 are
not required for installation
with the clean face kit.
Side mantle pieces may come
down along the outside of the
fireplace, with no restrictions as
to how they may protrude out
from the unit.