Electrical installation

24

© Lutz-Jesco GmbH 2020

BA-10491-02-V01

Piston diaphragm dosing pump  

MEMDOS KMS LB/LA

Operating instructions

9.2.2  Connection socket 2

9.2.2.1  Analogue input

The analogue input makes it possible to control the delivery capacity by 
means of a 0/4 – 20 mA signal. 

The delivery capacity is regulated via the stroke frequency.

0/4 - 20 mA signal

Tolerance ± 2 %

Working resistance: 500 ohms

Pin

M12x1 

(A-coded)

Assignments

Connection Cable colour*

2

(+) 0/4 – 20 mA

3

2

White

WH

3

Analogue (GND)

Blue

BU

Tab. 23:  Analogue input

* Applies to cable colours from Lutz-Jesco GmbH. No liability is accepted 
for cables from other manufacturers.

9.2.2.2  Analogue output

The dosing pump relays an analogue signal via the analogue output; its 
current value behaves in proportion to the delivery capacity set. With 0 % 
delivery capacity, 0 mA or 4 mA is registered. With 100 % delivery capac-
ity, the output signal amounts to 20 mA.

0/4 – 20 mA signal

Tolerance ± 2 %

Pin

M12x1 

(A-coded)

Assignments

Connection Cable colour*

1

0/4 – 20 mA

4

1

Brown

BN

4

Analogue (GND)

Black

BK

Tab. 24:  Analogue output

* Applies to cable colours from Lutz-Jesco GmbH. No liability is accepted 
for cables from other manufacturers.

9.2.3  Connection socket 3

9.2.3.1  Level input

The dosing pump can be connected with an external level contact (e.g. a 
suction line with a level switch) via the level input. The contact is open 
when not switched. 24 V DC are always applied to pin 3. If the float falls 
with a falling level, a contact is switched and the pump comes to a stand-
still. The alarm relay is also switched and the level and alarm LEDs illumi-
nate.

Closer NO

I

max

 (with 24 V) = 3 mA

Switching level high > 15 V DC

Pin

M12x1 

(A-coded)

Assignments

Connection

Cable colour*

2

DIG IN 2

IN

24 V

White

WH

3

24 V OUT

Blue

BU

Tab. 25:  Level input

* Applies to cable colours from Lutz-Jesco GmbH. No liability is accepted 
for cables from other manufacturers.

9.2.4  Connection socket 4

9.2.4.1  Alarm relay output

Faults of the dosing pump can be outputted via the alarm relay. An alarm 
LED lights up as soon as a fault is registered. The LED begins to flash 
once the fault has been remedied and the error can be cleared.

potential-free

With an ohmic resistive load: max. 230 V AC, 2.5 A / max. 30 V DC, 2.5 
A

Possible faults:

Level switch (empty notification)

Stroke sensor

Cable break

Motor overload

Damage to motor

Drive defective

Pin

M12x1 

(B-coded)

Assignments

Connection Cable colour*

1

Break (NC) 
contact

1

2

4

Brown

BN

2

Make (NO) 
contact

White

WH

3

-

Blue

BU

4

Changeover 
contact

Black

BK

Tab. 26:  Alarm relay output

* Applies to cable colours from Lutz-Jesco GmbH. No liability is accepted 
for cables from other manufacturers.

Summary of Contents for MEMDOS KMS LA

Page 1: ...uctions Lutz Jesco GmbH 2020 BA 10491 02 V01 Piston diaphragm dosing pump MEMDOS KMS LB LA Operating instructions Read the operating manual The user is responsible for installation and operation relat...

Page 2: ......

Page 3: ...Dimensions 17 6 1 MEMDOS KMS LB LA 17 7 Installing the Dosing Pump 18 7 1 Set up information 18 7 2 Installation on a wall console 18 8 Hydraulic installations 19 8 1 Design of the system 19 8 2 Gene...

Page 4: ...otentially hazardous situation Failure to follow this instruction may lead to death or severe injuries CAUTION Refers to a potentially hazardous situation Failure to follow this instruction may lead t...

Page 5: ...all the screw connections have been tightened correctly and are leak proof WARNING Caustic burns or other burns through dosing media While working on the dosing head valves and connections you may com...

Page 6: ...afety Data Sheets to the dosing media find out what protective equipment you need You will require the minimum of the following personal protective equip ment Personal protective equipment required Pr...

Page 7: ...isk ar eas and know all the relevant standards and regulations Above all they have the required specialist knowledge about explosion protection like for example ignition protection classes flash point...

Page 8: ...nsity of dosing media must be followed You must only use dosing media at temperatures above freezing point or below the boiling point of the re spective medium n The materials of the dosing pump and h...

Page 9: ...e n Operation made more difficult due to inadequate lighting or machines that are difficult to access n Delivery of dosing media for which the system is not designed n Delivery of particulate or conta...

Page 10: ...ettable 0 100 using the potentiometer n Operation of the pump via the operating panel n Signal LEDs for status operating and error display n Clearance input for external start stop n Analogue input an...

Page 11: ...discharge opening 4 at its upper end A downwards piston movement following a set partial stroke stroke adjustment unit works to displace the hydraulic fluid through the flow opening into the reservoi...

Page 12: ...P N Made in Germany 102A12345678 12345678012345 MEMDOS KMS Lutz Jesco GmbH 30900 Wedemark Am Bostelberge 19 Germany 8 13 12 11 2 3 4 5 6 9 10 1 7 T Fig 4 Rating plate MEMDOS KMS LB LA No Description...

Page 13: ...181 83 130 181 Suction lift for non gassing media mWs 2 Tab 9 Delivery capacity data MEMDOS KMS LB LA 5 2 Operating conditions and limits MEMDOS KMS LB LA 14 20 30 60 100 140 200 285 320 400 500 700 A...

Page 14: ...15 DN20 DN30 Tab 11 Other data MEMDOS KMS LB LA 5 4 Motor data 5 4 1 400 V 230 V three phase motors MEMDOS KMS LB 14 20 30 60 100 140 200 285 400 320 500 700 Power output kW 50 Hz 0 75 60 Hz 0 86 Spee...

Page 15: ...otection class IP55 Insulation class F Size 80 Flange Diameter mm 120 Shaft mm 19 x 40 Cooling IC 411 Weight kg 13 Tab 13 400 V 230 V three phase motors with frequency converter MEMDOS KMS LB 5 4 3 23...

Page 16: ...20 500 700 Power output kW 1 10 Speed rpm 1500 Nominal current A max 9 2 Voltage V1 208 230 Mains voltage DIN EC 60033 120 V 208 V version CSA and UL certified Frequency Hz 50 60 Operating mode S1 Pro...

Page 17: ...dosing pump MEMDOS KMS LB LA Operating instructions 6 Dimensions All dimensions in mm 6 1 MEMDOS KMS LB LA 568 A B 1021 785 210 250 272 308 13 5 Fig 5 Dimensional drawing MEMDOS KMS LB LA Size dosing...

Page 18: ...be vibration free and stable n There must be enough free space in the area of the dosing head and the suction and pressure valves for these parts to be easily disman tled if required The entire space...

Page 19: ...side is at least 1 bar than on the suction side PLEASE NOTE Locking of threads Stainless steel and plastic parts particularly those made of PVC that are bolted together in a detachable connection e g...

Page 20: ...ll valves have arrows on them these indi cate the flow direction These arrows must always point upwards 8 5 Hydraulic accessories The following chapter is intended to give you an overview of installat...

Page 21: ...lsation dampeners and ones with hose connections n Pipelines must not transfer any mechanical tensions onto the pulsa tion dampener 8 5 5 Priming aid Priming aids are particularly advisable n in the c...

Page 22: ...sult which could result in fatal injuries Earth the dosing pump drive motor and all metal parts along the suction and pressure piping route 9 1 Drive motor connection n The electrical connection compl...

Page 23: ...signal in a PLC stroke counting for batch mode The signal can also be used to detect the pump run One contact is closed per stroke and a 24 V DC voltage signal is issued n Closer NO n Short circuit p...

Page 24: ...he dosing pump can be connected with an external level contact e g a suction line with a level switch via the level input The contact is open when not switched 24 V DC are always applied to pin 3 If t...

Page 25: ...safety valve of the dosing head The MEMDOS KMS pumps are fitted with controllable safety valves as standard this protects the dosing pump and the motor against damage from overloading e g a closed sli...

Page 26: ...be started or stopped by pressing the Start or Stop key Precondition for action The pump assembly and installation have been completed success fully Perform the following working steps 1 Set the desi...

Page 27: ...ED illuminates 3 Press Start The function cable break is activated 10 7 2 Level monitoring You can connect an external level switch to the pump The level switch monitors the filling level of a contain...

Page 28: ...ashes Motor too hot The motor protection is activated and the mo tor stops n Allow the motor to cool n Then press Reset Start to restart the pump Flashes quickly Insufficient mains voltage The motor p...

Page 29: ...MEMDOS KMS LB LA Operating instructions LEDs illuminated Reason Consequence Solution Damage to the gear Motor stops n Replace the gears n Consult the Lutz Jesco GmbH service dept Proximity switch defe...

Page 30: ...whether undesirable reactions could occur between the actual dosing medium and the water At initial commissioning it is advisable to prime the pump without backpressure For this purpose we recommend i...

Page 31: ...2 F rdermengen anpassen 2 3 1 Fig 16 Adjusting the delivery rate Perform the following working steps 1 If the pump supplies at normal system pressure turn in the manual delivery rate adjustment unit u...

Page 32: ...might cause damage to the control unit or the motor Drain the oil completely through the oil outlet before you transport the dosing pump Perform the following working steps 1 Clean the device thorough...

Page 33: ...sure that is many times the rated one The dosing medium can escape in the case of material failure or wear on the dosing head the connection pipe or the seals that are used Carry out maintenance work...

Page 34: ...ormation and maintenance intervals 12 2 Change the oil Fig 17 Draining oil on the dosing pump Resources required Oil collecting pan Low viscosity oil of the viscosity class ISO VG100 SAE 40 Perform th...

Page 35: ...hand on the fan wheel of the electric drive to lift the piston and thereby to create suf ficient space 7 Remove the cylinder end cap 4 of the dosing head PLEASE NOTE Damage to the hose diaphragm Shar...

Page 36: ...The arrows on the valves must point upwards 4 Position the valves in the centre and retighten the valve bolts 5 If no further maintenance work is required on the pump fill the pump to the mark with oi...

Page 37: ...diameter Current supply interrupted Reconnect the current supply The drive motor s electrical data does not match that of the mains supply Check the electrical installation System backpressure too hi...

Page 38: ...supply The drive motor s electrical data does not match that of the mains supply Check the electrical installation Tab 33 Type of fault No stroke movement observed 13 1 5 Dosing pump delivery rate to...

Page 39: ...discharge connection of dosing pump Clean blocked injection nozzle Install pulsation dampeners to reduce pressure peaks if pipes are too long Check function of safety valves Tab 37 Type of fault The d...

Page 40: ...0 Backpressure Stroke adjust ment in Fig 22 Delivery characteristic curve MEMDOS KMS LB LA 14 0 5 10 15 20 25 0 10 20 30 40 50 60 70 80 90 100 Backpressure Stroke adjust ment in Fig 23 Delivery charac...

Page 41: ...0 50 100 150 200 250 300 350 400 0 10 20 30 40 50 60 70 80 90 100 Backpressure Stroke adjust ment in Fig 30 Delivery characteristic curve MEMDOS KMS LB LA 320 0 50 100 150 200 250 300 350 400 0 10 20...

Page 42: ...A presente declara o perde a sua validade em caso de altera o ao equipamento n o autorizada por n s EN EU Declaration of Conformity We hereby certify that the device described in the following complie...

Page 43: ...ason for repair Dosing medium Description Irritating Yes No Properties Corrosive Yes No We hereby certify that the product has been cleaned thoroughly inside and outside before returning that it is fr...

Page 44: ...Company Phone Date Address Contact person Manufacturer order no Date of delivery Device type Serial number Nominal capacity nominal pressure Description of fault Service conditions of the device Point...

Page 45: ...structions 6 Hydraulic accessories 20 Hydraulic installations 19 I Injection nozzle 20 Installation electrical 22 hydraulic 19 Installing the Dosing Pump 18 Intended purpose 8 Intended use 8 L Level m...

Page 46: ...Warnings General warnings 5 Marking 4 Warning sign Explanation 4 Warranty claim 44 Working in a safety conscious manner 6...

Page 47: ......

Page 48: ...ostelberge 19 D 30900 Wedemark Phone 49 5130 5802 0 info lutz jesco com www lutz jesco com Operating instructions MEMDOS KMS LB LA Copyright 2020 by Lutz Jesco GmbH 10490000_6 ld BA MEMDOS KMS LB 14 E...

Reviews: