Application Note #428
8
Lutron Technical Support Center
1.800.523.9466
®
CCI Assignment and Scene Banking
(continued)
Functionality:
Once in the CCI programming mode, the following options are available:
1. Make the button to which a CCI action is currently programmed do “nothing”:
• Hold the currently programmed button for 3 seconds to make the selected CCI action be
“nothing”.
• The wallstation will automatically move on to programming the next CCI action.
2. Change the button to which the CCI action is currently programmed:
• Hold a button for 3 seconds to make that button the currently programmed button for the
selected CCI action.
• The wallstation will automatically move on to programming the next CCI action.
3. Not changing the settings of the selected CCI action:
• Tap any button to move on to programming the next CCI action.
4. Assign a scene bank to the selected CCI action:
• Simultaneously hold the top and bottom buttons of a scene column for 3 seconds to make
that scene column “bank” when this CCI action happens.
Ex.
A Scene 1-3 column can become a Scene 4-6 column when CCI1 is closed, and back to a
Scene 1-3 column when CCI1 is open.
• The wallstation will automatically move on to programming the next CCI action.
5. Unassign a scene bank from the selected CCI action
• Simultaneously hold the top and bottom buttons of a scene column (that has been
programmed to “bank”) for 3 seconds.
• The wallstation will automatically move on to programming the next CCI action.
Note:
The wallstation will not always cycle through all four CCI options. The exception occurs when the
currently programmed button is a raise or lower button, or a fine tune button.
Ex.
If the currently programmed button is a lower button, “CCI closed” will be like pressing that lower
button (dimming the load) and “CCI open” will be like releasing it (stop dimming). In this case, the
wallstation would skip programming the “CCI1 open” (since it is automatically set) and jump to
programming “CCI2 closed.”
After the final (“CCI 2 Open”) action has been programmed, the wallstation will automatically return to
APM. Exit APM by simultaneously pressing and holding the top and bottom buttons of the column for
3 seconds (if it is a 1B column, hold the single button for 10 seconds). Once the hold time elapses, all
status LEDs and backlight LEDs will return to their appropriate settings in Normal Mode.