R
24
RadioTouch
TM
RTA-RS232 Programming and Operation Guide
Operation (continued)
Select a preset to store the lighting levels for the new
scene. Using presets 1 through 5 will allow the
presets to be accessed and modified from a tabletop
or wall control. Once a preset has been selected,
save the current pone levels to that preset.
For this example, we will use preset 4.
Issue the Set Preset Command:
Host sends
:SPS,9,4<CR>
RS232 replies ~OK
Return DIP switch 1 to the up position on each
controller, or issue Preset Adjust Mode Exit
command.
Exit Preset or Adjust Mode:
Host sends
:PSA,9,EXIT<CR>
RS232 replies ~OK
The scene has now been programmed. Recall the
scene by issuing a Preset command for the Zone
that contains the scene.
In this example, the scene was stored in zone 9,
preset 4.
To Recall the Scene with the Preset Command:
Host sends
:PS,9,4<CR>
RS232 replies ~OK
If another scene containing the same lighting zones
is desired, the same process can be used as above,
selecting a different preset. If a scene containing
different lighting zones is desired, the same process
can be used, selecting a different zone on the RTA-
RS232 and a different preset.
Set Up Scenes
(not accessed from
Tabletop/Wall Control, multiple zone types)
It is possible to generate scenes that cannot be
accessed from other Tabletop or Wall Controls in the
system or that contain different zone types, i.e.
Lights and
Sivoia QED
shades (contact closure zone
type). However, to recall the scene, more than one
command must be issued. To set the scene, multiple
explicit commands will be issued.
Example:
A room has the following lighting zones addressed to
the RTA-RS232 interface:
Zone Description
Level for New Scene
0
Front lights
25%
1
Rear lights
80%
2
Wall washers
50%
3
Shades
Open
To accomplish this you will need to send the
following command lines in rapid succession:
Host sends
:XC,0,25<CR>
RS232 replies ~OK
Host sends
:XC,1,80<CR>
RS232 replies ~OK:
Host sends
:XC,2,50<CR>
RS232 replies ~OK
Host sends
:PS,3,3<CR>
RS232 replies ~OK
Set DIP switch 1 to
down position
RadioTouch
controller
R
adioTouch
TM
Coopersburg, PA 18036 USA
RTA-RX-F
LISTED 243C
I
nd. Cont. E q.
®
CONFIGURACIONES
REGLAGES
SETTINGS
PWR
STAT
PROG
100 H
r/100%
1 2
3
4
5
6 7
8
O
cc
.
C
o
m
O
cc
. S
ig
24
V
C
ir
C
o
m
+
_
0-10
V
PS S
ig
PELV (
C
lass
2
:
U
S
A
)
P/N 500-10633 © 2006 Lutron Electronics Co., Inc.
1
2
3
4
5
ON
USA, Canada
1-800-523-9466
Mexico
1-888-235-2910
www.lutron.com
15
V
®
Refer to the Installers Guide for more
detailed instructions.
Consulte la Guía de Instaladores para
información más detallada.
Référer au Guide d’installation pour plus de
renseignements détaillés.
120/277 V 60 Hz
16 A Max.
1
2
3
4
5
6
7
8
1
2
3
4
5
ON