Installation
2.1
Prerequisites
Vanderbilt SPC panel with firmware >= 3.6 (3.6 was the first version with support for FlexC)
Network router with DHCP server enabled
SPC Bridge and SPC panel connected to same local network
Internet access (to be able to use time synchronization via NTP)
KNX system
KNX configuration tool ETS v 5
2.2
First Time Installation Workflow
1.
Read carefully
End-User License Agreement for SPC Bridge (EULA)
in last section in this document. If
you do not agree to the terms of the EULA, do not install or use the SPC Bridge.
2.
Connect the included KNX interface, Weinzierl 332 or 312, to the SPC Bridge USB port.
3.
Connect the KNX bus cable to the KNX bus connector on the KNX interface.
NOTE!
The default
individual device address of the KNX interface is
15.15.255
. If this address already is in use you should
change the address (see section KNX Interface Info) before you connect the interface to the KNX-bus.
4.
Connect the SPC Bridge LAN port, with a regular network cable, to your network switch or router.
5.
Power up the device by connecting the included power adapter to a wall socket and then to the SPC
Bridge.
6.
Wait (~3 minutes) until the SPC Bridge has fully started.
7.
Open a web browser and access your router (DHCP-server) to find the IP address assigned to the SPC
Bridge. Type the IP address in the web browser to go to the SPC Bridge sign in page.
8.
Assign a static IP address to the SPC Bridge. Follow instructions in section
System Administration,
Static IP Address
.
9.
Configure SPC communication. Follow the instructions in section
SPC Bridge Configuration, SPC
Communication
.
10.
Test the SPC Communication. See
SPC Communication Test
.
11.
Configure the KNX interface. Follow the instructions in
ETS KNX configuration