SPC Bridge KNX User Manual
Revision
1.0
Page
10 of 25
Reference
2020-111
4
SPC Bridge Configuration
4.1
SPC Bridge Sign In
Type IP address of the SPC Bridge in the web browser address field, go to SPC Bridge sign in page,
enter username (
spcbridge
) and password (default
Spcbridge!
) and click
Login
.
4.2
SPC Communication (FlexC)
To setup the communication link between SPC Panel and SPC Bridge you have to configure the link in
both SPC Panel and SPC Bridge ends.
4.2.1
SPC Panel - FlexC Settings.
Use
Vanderbilt SPC Web interface
and define the FlexC communication following this instructions:
1.
Select Full Engineer mode
2.
Create a specific user for the SPC Bridge communication, e.g
spcbridge
. User profile should be
Manager and you need also to define a web password for the user. (To be able to set a web password
you need to login as the user in the SPC web interface).
3.
Select
Communications -> FlexC -> Event Profiles
. Click on
Add
to add a new event profile. Give the
event profile the name
SPC Bridge Events
and select (check) the report checkboxes for all event
types. (You may consider reducing these settings later to just necessary events for the application)
4.
Select
Communications -> FlexC -> FlexC ATS
. Select
Add Custom ATS
and change following from
the default settings:
- ATS Name = SPC Bridge
- Event Profile = SPC Bridge Events (created in step 3)
- ATS Polling Timeout = 60 seconds
- Uncheck Generate FTC and Re-queue Events