SPC Bridge KNX User Manual
Revision
1.0
Page
19 of 25
Reference
2020-111
reported in “Zone command reply status”.
23
Zone isolate
command
ID of zone to isolate
The success/error of the command is
reported in “Zone command reply status”.
DPT 5
1-byte
C-W--
24
Zone deisolate
command
ID of zone to deisolate
The success/error of the command is
reported in “Zone command reply status”.
DPT 5
1-byte
C-W--
30
Zone command
reply status
0 = Last zone command succeeded,
1-255 = Zone command failed error code.
Codes are listed in section 7.1 SPC Command
Error Codes.
DPT 5
1-byte
CR-T-
Zone ID = 1 to maximum number of zones (128).
5.2.5
SPC Area Status Objects
For
each SPC area
following Group Objects will be available:
Relative
address *
Name
Values
Datapoint Type
Length
Flags
+1
Area X unset
0 = Area is not unset,
1 = Area is unset (disarmed)
DPT 1
1-bit
CR-T-
+2
Area X partset A
0 = Area is not partset A,
1 = Area is partset A
DPT 1
1-bit
CR-T-
+3
Area X partset B
0 = Area is not partset B,
1 = Area is partset B
DPT 1
1-bit
CR-T-
+4
Area X fullset
0 = Area is not fullset,
1 = Area is fullset (armed)
DPT 1
1-bit
CR-T-
+5
Area X intrusion
alarm
0 = Area has no intrusion alarm **,
1 = Area has at least one intrusion alarm **
DPT 1
1-bit
CR-T-
+6
Area X fire alarm
0 = Area has no fire alarm ***,
1 = Area has at least one fire alarm ***
DPT 1
1-bit
CR-T-
+7
Area X tamper
alarm
0 = Area has no tamper alarm ****,
1 = Area has at least one tamper alarm ****
DPT 1
1-bit
CR-T-
+8
Area X confirmed
alarm
0 = Area has no confirmed alarm **,
1 = Area has at least one confirmed alarm **
DPT 1
1-bit
CR-T-
+13
Area X unset user id
1 – 255 = SPC User ID of user who last unset
the area,
0 = User Id is unknown
For user ids > 255 (e.g the FlexC user) the
value will be 255.
Will be sent to KNX bus every time Area
mode changes to Unset and if value changes
of other reason e.g at startup.
DPT 5
1-byte
CR-T-
+14
Area X fullset user
id
1 – 255 = SPC User ID of user who last fullset
the area,
0 = User Id is unknown
DPT 5
1-byte
CR-T-