N32O
User's manual
21
Table 5
,
,
,
Parameter
symbol
Description
Range of changes
Input value controlling the alarm.
Default: IND 1
IND 1
– measuring value on the main input converted by the
mathematical functions, individual characteristics and without
averaging using the moving window method.
Note: Averaging is not active for the counter type
measurement modes.
AVG 1
– the same as
IND 1
, but averaged using the moving
window method.
VAL 1
–
measuring value on the main input (I1) without
conversion and without averaging, calculated only by
CONSt
parameter.
EXt 1
– value additionally measured on the main input (e.g. a
frequency during the period measurement).
IND 2
– measuring value on the additional input converted by
the mathematical functions, individual characteristics and
without averaging using the moving window method.
Note: Averaging is not active for the counter type
measurement modes.
AVG 2
– the same as
IND 2
, but averaged using the moving
window method.
VAL 2
–
measuring value on the additional input (I2) without
conversion and without averaging, calculated only by
CONSt
parameter.
EXt 2
– value additionally measured on the additional input
(e.g. a frequency during the period measurement).
tIME
– current RTC time in hh.mmss format.
Note:
The averaging period is defined by
MAVG
setting.
Alarm type (see section 5.4.3)
Default: H-oFF
n-on
– normally enabled
n-oFF
– normally disabled
on
– enabled
oFF
– disabled
H-on
– permanently enabled (manually)
H-oFF
– permanently disabled (manually)
REG
– the state controlled by the MODBUS protocol register.
Alarm state change lower threshold.
Default: 10
-99999…999999
Alarm state change upper threshold.
Default: 20
-99999…999999
Alarm activation delay - the duration in
seconds of the alarm state before activating
the alarm relay.
Default: 0
0…900
Alarm deactivation delay - the duration in
seconds the state without the alarm before
deactivating the alarm relay.
Default: 10
0…900
Alarm signalization latch. When the function is
enabled, after the alarm event ends, the
display indicator informing about the alarm
status will be flashing signaling the alarm until
it is canceled by a combination of buttons
or via the RS-485 interface.
Default: OFF
ON
– alarm memory is activated.
OFF
– alarm memory is deactivated.