N32O
User's manual
18
only data acquisition period for the averaging
algorithm using the moving window method.
Number of the item for moving window method
averaging. Each item is a measurement taken
in SAVG time.
Note: The averaging using the moving window
method is disabled for the counter types.
However, the minimum and maximum value in
the time period set by MAVG setting is saved.
Default: OFF
Mathematical function selection which should
be applied for the measuring value. The
mathematical function is applied before the
value is converted by the individual
characteristic.
Note: The setting has no effect in
W tIME
and
tIME
modes.
Default: NONE
NONE
– no additional mathematical operations.
Sqr
– measuring value is squared.
Sqrt
– square root of the measuring value.
Inv
– reciprocal of the measuring value.
InvSq
– reciprocal of the measuring value is squared.
InvSt
– square root of reciprocal of the measuring value.
The setting applies only to
CNtFL
mode which
is available only for the input 1, and determines
the period for which the input pulses speed
(frequency) is to be converted. For example,
the measuring value would be 600 at 10 pulses
per second and the setting
/min
.
Default: /SEC
/SEC
– conversion of the pulse speed for one second period.
/MIN
– conversion of the pulse speed for one minute period.
/HOUR
– conversion of the pulses speed for one hour period.
Table 2
Parameter
symbol
Description
Range of changes
The function of the input no. 3 (terminal I3).
Each pulse on this input increases the counter
no. 3, regardless of the function of the input.
The functions assigned to the input refer to the
control of the inputs configured to work in the
counter mode.
Default: NONE
NONE – no function
C1 SS, C2 SS
– control of the main input (counter modes).
An active signal at the input starts the counter and counting.
The counter is stopped at no signal at the input - the pulses
are not counted. The counter operation is controlled by the
input level.
C1 STA, C2 STA
– start the counter. Edge control - input
signal starts the counter.
C1 STP, C2 STP
– stop the counter. Edge control - input
signal stops the counter.
C1 RST, C2 RST
– input signal resets the counter. The initial
value of the counter (after a reset) depends on set counting
direction (see the parameter
CONSt
) .
C2 DIR
– change counting direction. During an active signal
the counting direction of the additional input of the counter
(I2) is changed.
C12SS
– control of the main input and the additional input
(counter modes). An active signal at the input starts the
counters and counting the pulses. The counters are stopped
at no signal at the input - the pulses are not counted. The
counters are controlled by the level.
Note: C1 refers to the main input (I1) and C2 refers to the
additional input (I2).
Minimum duration of a low level on meter input
I3 before it is considered as the low level.
Pulses with a shorter low level duration are
ignored.
The setting is expressed in milliseconds.
Default: 10
0…65535
Minimum duration of a high level on meter
input I3 before it is considered as the high
level. Pulses with a shorter high level duration
are ignored.
The setting is expressed in milliseconds.
Default: 0
The function of the input no. 4 (terminal I4).
Default: NONE