Power Up: DLP-513
363-205-401
Page 8 of 8
Issue 7, March 1997
32. On battery shelf, connect DMM test leads to +BAT jack (J5) and
−
BAT jack
(J6).
33. Does meter indicate greater than 45.0 volts DC?
If YES, then proceed to Step 37.
If NO, then continue with Step 34.
34. Have all battery packs been replaced?
If YES, then continue with Step 35.
If NO, then proceed to Step 36.
35. Check battery lead connections at battery shelf. Repeat procedure from Step
27 after locating and correcting trouble.
36.
NOTE:
If voltage requirements are not met after replacement battery pack is
installed, original battery pack should be reinstalled in battery shelf.
Select another battery pack on battery shelf and repeat from Step 31.
37. Remove DMM test leads.
38. Install good 25-Amp fuses (Buss ABC or equivalent) into +BAT and
−
BAT
fuse holders on battery shelf.
39. Install good 5-Amp fuse into HTR fuse holder on battery shelf.
40. Insert connector J113 into connector P113 on battery shelf.
STOP. YOU HAVE COMPLETED THIS PROCEDURE.