CHECKING CHILD DEVICE LINK QUALITY
You can check the link quality: for every device directly linked to the
FI750/RF/W2W
:
CHECKING BACKGROUND NOISE
You can check the background noise measured in the channels used by the
FI750/RF/W2W
:
25
[Main Menu]
System Status
[System Status]
Child device LQ
01
-
47 | >
-
75
4
02
-
80 |
-
75÷
-
85 3
RF
→
EXP |
→
DEV
M
RF
RF Address of the chid device: it can go from 1 to 32
F
after the RF address indicates that the device with this address is in link fault
*
after the RF address indicates that after entering the menu the device with this RF address has communicated
with mark
≤2
→
EXP
Indicates the link power (dBm) of the last communication received by the
),5)::
→
DEV
Indicates the link power of the last communication received by the device from the
),5)::
.
The possible values shown are:
>
-
75
Link power
≥
-
75dBm
-
75÷
-
85
-
85 dBm
≤
Link power <
-
75dBm
-
85÷
-
100
-
100 dBm
≤
Link power <
-
85dBm
-
100÷
-
105
Link power <
-
100dBm
The value is the
“
translation
”
of the link mark to the dBm interval.
M
Indicates the link mark of the last communication received by the device from the
),5)::
.
The possible values shown are:
4 Excellent link quality
3 Good link quality (minimum mark for a reliable link)
2 Poor link quality
1 Bad link quality
[Main Menu]
System Status
[System Status]
Background noise
FIELD CHA:
-
117
CHB:
-
119
NET CHA:
-
120
CHB:
-
117
FIELD CHA:
Indicates the background noise (dBm) measured in the channel A of the field channel pair
CHB:
Indicates the background noise (dBm) measured in the channel B of the field channel pair
NET CHA:
Indicates the background noise (dBm) measured in the channel A of the network channel pair
CHB:
Indicates the background noise (dBm) measured in the channel B of the network channel pair