Chapter 8 Table of Functions
8-22
No. Comm. No.
Function
Display
Name
Setting Range
Initial
Value
Shift in
Operatio
n
Control Mode
V/F
SL VC
SLT
VC
T
08
0h1608
AO2 Gain analog output 2 gain
-1000 ~ 1000 [%]
80.0 O
O
O
O
O
O
09
0h1609
AO2 Bias analog output 2bias
-100 ~ 100 [%]
20.0 O
O
O
O
O
O
10
0h160A AO2 Filter analog output 2 filter
0 ~ 10000 [ms]
5 O
O
O
O
O
O
11
0h160B AO2Const
%
analog constant output 2
0 ~ 100 [%]
0.0 O
O
O
O
O
O
12
0h160C
AO2
Monitor analog output 2 monitor
0 ~ 1000 [%]
0.0 O
O
O
O
O
O
14
Note25)
0h160E AO3 Mode analog output3 item
0 Frequency
0 :
Frequency O
O
O
O
O
O
1 Current
2 Voltage
3 DC Link Volt
4 Torque
5 Watt
6 Idse
7 Iqse
8 Target Freq
9 Ramp Freq
10 Speed Fdb
11 Speed Dev
12 PID Ref Value
13 PID Fbk Value
14 PID Output
15 Constant
15
0h160F AO3 Gain analog output 3 gain
-1000 ~ 1000 [%] 100.0 O
O
O
O
O
O
16
0h1610
AO3 Bias analog output 3bias
-100 ~ 100 [%]
0.0 O
O
O
O
O
O
17
0h1611
AO3 Filter analog output 3 filter
0 ~ 10000 [ms]
5 O
O
O
O
O
O
18
-
AO3 Const % analog constant output 3
0 ~ 100 [%]
0.0 O
O
O
O
O
O
19
0h1613
AO3 Monitor analog output 3 monitor
-1000 ~ 1000 [%]
0.0 O
O
O
O
O
O
20
0h1614 AO4 Mode analog output4 item
0 Frequency
0 :
Frequency -
O
O
O
O
O
1 Current
2 Voltage
3 DC Link Volt
4 Torque
5 Watt
6 Idse
7 Iqse
8 Target Freq
9 Ramp Freq
10 Speed Fdb
11 Speed Dev
12 PID Ref Value
13 PID Fdb Value
14 PID Output
15 Constant