Chapter 8 Table of Functions
8-2
No. Comm. No. Function Display
Name
Setting Range
Initial Value
Shift in
Operation
Control Mode
V/F
SL VC
SLT
VC
T
10 0h110A
Torque
Control
torque control
0
No
0 : No
X
X X X O O
1
Yes
11 0h110B
Jog
Frequency jog frequency
0.5 ~ max. freq.[Hz]
10.00 O
O O O O O
12 0h110C Jog Acc Time jog operation
Acc time
0 ~ 600 [s]
20.0 O
O O O O O
13 0h110D Jog Dec Time jog operation
Dec time
0 ~ 600 [s]
30.0 O
O O O X X
14 0h110E
Motor
Capacity
motor capacity
0: 0.2kW,
2: 0.75kW,
4: 2.2kW,
6: 5.5kW,
8: 11kW,
10: 18.5kW,
12: 30kW,
14: 45kW,
16: 75kW,
18: 110kW,
20: 160kW,
22: 220kW,
24: 315kW,
26: 450kW
1: 0.4kW
3: 1.5kW
5: 3.7kW
7: 7.5kW
9: 15kW
11:22kW
13:37kW
15: 55kW
17: 90kW
19: 132kW
21: 185kW
23: 280kW
25: 375kW
depends on
inverter
capacity
X
O O O O O
15 0h110F Torque Boost torque boost
method
0 Manual
0: Manual
X
O X X X X
1 Auto
16
Note2)
0h1110
Fwd Boost forward torque
boost
0 ~ 15 [%]
Below 75kW 2.0
X
O X X X X
Above 90kW 1.0
17
0h1111
Rev Boost reverse torque
boost
Below 75kW 2.0
X
O X X X X
Above 90kW 1.0
18
0h1112
Base Freq base frequency
30 ~ 400 [Hz]
60.00
X
O O O O O
19
0h1113
Start Freq Start frequency
0.01 ~ 10 [Hz]
0.50
X
O X X X X
20
0h1114
Max Freq maximum
frequency
40 ~ 400
60.00
X
O O O O O
21
0h1115 Hz/Rpm Sel speed
unit
selection
0 Hz Display
0: Hz O
O O O O O
1 Rpm Display
25
0h1119
Output Freq
Monitoring the Output
Speed
0~Max Freq[Hz]
0.00Hz
O
O O O O O
* The grey code refers to hidden code, emerging only in case of setting of the code.
Note 2)
DRV-16-17 code is displayed only when DRV-15 (Torque Boost) code value is “Manual”.