Chapter 8 Table of Functions
8-8
No.
Comm.No.
Function Display
Name
Setting Range
Initial Value
Shift in
Operation
Control Mode
V/F
SL
VC
SLT
VC
T
24 0h1318
Freq Limit frequency limit
0
No
0:No X O O O X X
1
Yes
25
Note10)
0h1319 Freq Limit Lo frequency lower limit
0 ~ upper limit [Hz]
0.50 O O O O X X
26 0h131A Freq Limit Hi frequency upper limit
0.5 ~ max. freq. [Hz]
60.00 X O O O X X
27 0h131B
Jump Freq frequency jump
0
No
0:No X O O O X X
1
Yes
28
Note 11)
0h131C
Jump Lo 1 jump freq. lower limit 1
0 ~ jump freq.
upper limit 1 [Hz]
10.00 O O O O X X
29 0h131D
Jump Hi 1 jump freq. upper limit 1
Jump freq. lower limit 1
~ max. freq. [Hz]
15.00 O O O O X X
30 0h131E
Jump Lo 2 jump freq. lower limit 2
0 ~ jump freq.
upper limit 2 [Hz]
20.00 O O O O X X
31 0h131F
Jump Hi 2 jump freq. upper limit 2
Jump freq. lower limit 2
~ max. freq. [Hz]
25.00 O O O O X X
32 0h1320
Jump Lo 3 jump freq. lower limit 3
0 ~ jump freq.
upper limit 3 [Hz]
30.00 O O O O X X
33 0h1321
Jump Hi 3 jump freq. upper limit 3
Jump freq. lower limit 3
~ max. freq. [Hz]
35.00 O O O O X X
41
Note12)
0h1329 BR Rls Curr brake open current
0 ~ 180.0 [%]
50.0 O O O O X X
42 0h132A
BR Rls Dly brake open delay time
0 ~ 10.00 [s]
1.00 X O O O X X
44 0h132C BR Rls Fwd Fr brake open
forward frequency
0 ~400 [Hz]
1.00 X O O O X X
45 0h132D BR Rls Rev Fr brake open
reverse frequency
1.00 X O O O X X
46 0h132E BR Eng Dly brake close delay time
0 ~ 10 [s]
1.00 X O O O X X
47 0h132F
BR Eng Fr brake close frequency
0 ~400 [Hz]
2.00 X O O O X X
50 0h1332 E-Save Mode energy saving operation
0
None
0: None X O O X X X
1
Manual
2
Auto
51
Note13)
0h1333 Energy Save energy saving amount
0 ~ 30 [%]
0 O O O O X X
60 0h133C Xcel Change
Fr
Acc/Dec time exchange
frequency
0 ~ max. freq. [Hz]
0.00 X O O O X X
* The grey code refers to hidden code, emerging only in case of setting of the code.
Note 8)
ADV-12 is displayed only when ADV-07 “Stop Mode” is set as “Dc-Start”.
Note 9)
ADV-14~17 is displayed only when ADV-08 “Stop Mode” is set as “DC-Brake”.
Note 10)
ADV-25~26 is displayed only when ADV-24 (Freq Limit) is set as “Freq Limit”.
Note 11)
ADV-28~33 is displayed only when ADV-27 (Jump Freq) is set as “Yes”.
Note 12)
ADV-41~47 is displayed only when a code of OUT-31~33 is set as “BR Control”.
Note 13)
ADV-51 is displayed only when ADV-50 (E-Save Mode) is set as values other than “None”.