Chapter 6 Basic Functions
6-17
3) Setting of Acc/Dec Time by using Multi-Function Terminal Based on Operating
Frequency
Group
Code
No.
Function Display
Setting Display
Setting
Range
Unit
DRV
03
Acc Time
-
Below
75kW
20.0
0~600
sec
Above
90kW
60.0
DRV
04
Dec Time
-
Below
75kW
30.0
0~600
sec
Above
90kW
90.0
BAS
70~82
Acc Time-x
-
x.xx
0~600
sec
BAS
71~83
Dec Time-x
-
x.xx
0~600
sec
IN
65~75
Px Define
11 XCEL-L
-
-
IN
65~75
Px Define
12 XCEL-M
-
-
IN
65~75
Px Define
49 XCEL-H
-
-
IN
89
In Check Time
-
1
1~5000
msec
* Acc Time-x : Acc Time-1~3, Dec Time-x: Dec Time-1~3
Using the multi-function terminal, you can change deceleration time.
You can set the time of acc/dec - 0 in Drive Group -03 and -04 and the time of acc/dec –
1~3 in Drive Group -70 ~75.
Choose the terminal for using acc/dec time command between multi-function
terminals(P1~P11), and one of the multi- acc/dec command should be set.
XCEL-L and XCEL-M are recognized as a binary code, the acc/dec time will be operated
as set in BAS-70~75.
Multi-function terminal P7and P8, respectively, operate as below if XCEL-L and XCEL-M
are set.
Acc/Dec Time P8
P7
0
-
-
1
-
2
-
3