Chapter 14. COM Option (RS-485)
14-1
14.
COM Option (RS-485)
14.1
Introduction
SV-iE5 inverter can be controlled and monitored by the sequence program of the PLC or other master module. Drives
or other slave devices may be connected in a multi-drop fashion on the RS-485 network and may be monitored or
controlled by a single PLC or PC.
14.2
Specifications
z
Performance Specifications
Item
Specification
COM method
RS-485
Transmission form
Bus method, Multi drop Link System
Inverter SV-iE5
series
Converter RS232
converter
Connectable drives
Max. 16
Transmission distance
Max. 1,200m (within 700m recommended)
z
Hardware specification
Item
Specification
Installation
Use S+, S- terminals on control terminal block
Power supply
Use Insulated power from the inverter power supply
z
Communication specification
Item
Specification
Communication speed
9,600/4,800/2,400 bps selectable
Control procedure
Asynchronous communication system
COM system
Half duplex system
Character system
Binary (Modbus RTU), ASCII (LSBUS)
Stop bit length
1 bit / 2bit
CRC check
2 bytes
Parity check
None