EMI / RFI POWER LINE FILTERS
LS inverters, iE5 series
CAUTION
RFI FILTERS
RECOMMENDED INSTALLATION INSTRUCTIONS
To conform to the EMC directive, it is necessary that these instructions be followed as closely as possible. Follow the usual safety
procedures when working with electrical equipment. All electrical connections to the filter, inverter and motor must be made by a qualified
electrical technician.
1- ) Check the filter rating label to ensure that the current, voltage rating and part number are correct.
2- ) For best results the filter should be fitted as closely as possible to the incoming mains supply of the wiring enclousure, usually directly
after the enclosures circuit breaker or supply switch.
3- ) The back panel of the wiring cabinet of board should be prepared for the mounting dimensions of the filter. Care should be taken to
remove any paint etc... from the mounting holes and face area of the panel to ensure the best possible earthing of the filter.
4- ) Mount the filter securely.
5- ) Connect the mains supply to the filter terminals marked LINE, connect any earth cables to the earth stud provided. Connect the filter
terminals marked LOAD to the mains input of the inverter using short lengths of appropriate gauge cable.
6- ) Connect the motor and fit the ferrite core ( output chokes ) as close to the inverter as possible. Armoured or screened cable should be
used with the 3 phase conductors only threaded twice through the center of the ferrite core. The earth conductor should be securely
earthed at both inverter and motor ends. The screen should be connected to the enclousure body via and earthed cable gland.
7- ) Connect any control cables as instructed in the inverter instructions manual.
IT IS IMPORTANT THAT ALL LEAD LENGHTS ARE KEPT AS SHORT AS POSSIBLE AND THAT INCOMING MAINS AND OUTGOING
MOTOR CABLES ARE KEPT WELL SEPARATED.
THE LS RANGE OF POWER LINE FILTERS FF ( Footprint ) - FE ( Standard ) SERIES, HAVE BEEN SPECIFICALLY DESIGNED WITH HIGH
FREQUENCY LG INVERTERS.
THE USE OF LS FILTERS, WITH THE INSTALLATION ADVICE OVERLEAF HELP TO ENSURE TROUBLE FREE USE ALONG SIDE SENSITIVE
DEVICES AND COMPLIANCE TO CONDUCTED EMISSION AND IMMUNITY STANDARS TO EN 50081.
THE LS RANGE OF POWER LINE FILTERS FF ( Footprint ) - FE ( Standard ) SERIES, HAVE BEEN SPECIFICALLY DESIGNED WITH HIGH
FREQUENCY LG INVERTERS.
THE USE OF LS FILTERS, WITH THE INSTALLATION ADVICE OVERLEAF HELP TO ENSURE TROUBLE FREE USE ALONG SIDE SENSITIVE
DEVICES AND COMPLIANCE TO CONDUCTED EMISSION AND IMMUNITY STANDARS TO EN 50081.