Chapter 7. Function List
7-8
z
PG Group
Display Name
Min/Max
range
Description
Factory
defaults
Adj.
during
run
Page
P38 Number of
Auto Restart
try
0 ~ 10
It sets the number of restart tries after a
fault occurs. Auto Restart is deactivated
if the fault outnumbers the restart tries.
This function is active when [drv] is set to
1 or 2 {Run/Stop via control terminal}.
0
1)
O
P39 Auto
Restart
time
0 ~ 60 [sec] Restart tries after auto restart waiting
time has passed.
1.0 O
10-12
P40 Motor cap.
select
0.1~ 0.4
[kW]
Selects the capacity of a motor to use.
2)
X
P41 Number of
motor poles
2 ~ 12
It is displayed via rpm in drive group.
4
X
P42 Rated slip
frequency
0 ~ 10
[Hz]
Enter the difference between the input
power frequency and the value
calculated by converting rpm described
in the nameplate to frequency.
3)
X
P43 Motor
rated
current
0.0~ 25.5
[A]
Enter motor rated current on the
nameplate.
-
X
P44 No Load
Motor Current
0.0 ~ 25.5
[A]
Enter the current value detected when
the motor is rotating in rated rpm after
the load connected to the motor shaft is
removed.
Enter the 50% of the rated current value
when it is difficult to measure No Load
Motor Current.
-
X
10-6
P45 Carrier
frequency
select
1 ~ 10
[kHz]
It selects the audible sound of the motor.
If the set value is higher, the inverter
sound is quieter but the noise from the
inverter and leakage current will become
greater.
3 O
10-13
1)
No auto restart in case of protection functions such as OHt, Lvt, ESt, HWt.
2)
P40 initial value is preset based on inverter rating.
3)
P42 ~ P44 values are changed based on the P40. factory defaults are set based on the inverter capacity.