Chapter 6 P2P service
6-30
Sequen
ce
Setting
process
Setting method
4
HEAD,TAI
L
Register
BODY
1) Click Add Frame and select the frame type HEAD, TAIL, BODY to create.
2)The name of the frame edit window becomes active only if the type is BODY.
3) A number of BODY's can be created by using a different name.
5
Add
segment(
HEAD)
1) Double click the HEAD item in the project tree to create the segment
setting screen.
2) In addition to the segment, the type is a numeric constant that represents
the Hex value in ASCII code, and the data is the Hex value of 2, which means
STX.
6
Add
segment(
TAIL)
1) In DRS.TAIL, type is numeric constant represented by Hex ASCII code
and data is input Hex value D, A which means CR and LF.
7
Add
segment(
BODY)
1) Since the present value is saved in MB200 and the set value in MB210,
set the storage area of the 1st and 2nd data.
2) Since the data size of 1,2 is 4 bytes, set the size as 4 as a fixed sized
variable when entering into the segment.
3) Check the memory assignment to select the data storage area.
8
Receive
total
frame
This is the result of writing the whole frame of response that receives data
response by the temperature controller.
Summary of Contents for XGL-EFMF
Page 17: ...Table of Content 16 ...
Page 27: ...Chapter 1 Overview 1 10 ...
Page 39: ...Chapter 2 Product specifications 2 12 4 XOL ES4T XOL ES4H 2 1 3 3 4 5 6 7 8 9 10 ...
Page 108: ...Chapter 4 Smart Extension service 4 19 The opposite case is indicated by a blue line ...
Page 135: ...Chapter 4 Smart Extension service 4 46 ...
Page 174: ...Chapter 5 High speed link service 5 35 ...
Page 197: ...Chapter 6 P2P service 6 14 Then select Online Change Mode to run ...
Page 227: ...Chapter 6 P2P service 6 44 ...
Page 289: ...Chapter 7 server service 7 62 ...
Page 358: ...Appendix A 25 A 6 Dimension 1 XGL EFMTB EFMFB XGL EH5T Unit mm ...
Page 359: ...Appendix A 26 2 XOL ES4H Unit mm ...
Page 360: ...Appendix A 27 3 XOL ES4T Unit mm ...
Page 361: ...Appendix A 28 ...
Page 363: ...Warranty and Environment Policy 2 ...